Installing the DMS

Connecting the Centralized Controller
The centralized controllers must be installed to control the
indoor units.
1
Loosen the two screws on the bottom of the DMS front
cover.
2
Hold the bottom two sides of the DMS and push upwards
to slide open the cover. (Sliding type cover)
3
Connect the provided power cable to the power terminal.
4
Connect the C1, C2 communication cable from the
centralized controller to the J1 terminal of the DMS.
(Communication will fail if the cable is not connected
properly.)
5
Connect the LAN cable to the J6 terminal of the DMS.
6
Close the case cover after making sure the power cable is
not pressed.
7
Assemble the cover as shown in the picture to avoid
exposure of the stripped wires.
Caution
Maximum 16 centralized controllers can be connected
to one DMS.
Separate the power cable and the communication cable
when installing the DMS. (The DMS may malfunction
due to electrical disturbance.)
Centralized controller
communication cable
POWER CABLE
LAN CABLE