FORCED COOLING
In order to accumulate refrigerant, units operate in cooling cycle.
G
Execution condition and operation status are shown below.
[Execution condition]
With neither indoor unit 1 and 2 not operated, when forced cooling switch is turned ON, forced cooling will
G
be performed.
Always operation status of indoor unit are monitored and forced cooling is inhibited when operation of
G
any unit is detected.
[Operation status]
Outdoor unit fan: Fixed in LO.
G
Compressor rotation speed: Fixed in 3900min
G
[Note]
During forced cooling, if failure occurs in outdoor unit, thermostat is turned off. However, it is not counted.
G
Since rotation speed of compressor is fixed in 3900min
G
control at start is not performed.
–1
.
–1
during forced cooling, compressor fixed speed
– 39 –