(1) 30 seconds after the operation is started, when the room temperature is (cooling preset temperature) - (1.33˚C) or less, the operation is
done assuming as the preset temperature = (room temperature at the time) - (2˚C).
(2) The indoor fan is operated in the "Lo" mode, OFF for 5 minutes and ON for 1 minule (at high humidity) or OFF for 6 minutes and ON for
1 minute (at low humidity), repeatedly acoording to the humidity judgement when the thermostat is turned OFF.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor
operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.