Hide thumbs Also See for RBC-TRP100E:

Advertisement

AIR CONDITIONER (SPLIT TYPE)

Installation manual

Branch kit 1:3
Model name:
RBC-TRP100E
Installation manual
Air conditioner
(Split type)
Manuel d'installation
Climatiseur
(Type split)
Installationshandbuch
Klimagerät
(Split-typ)
Manuale di installazione
Condizionatore d'aria
Manual de instalación
Aire acondicionado
(Tipo split)
Manual de Instalação
Ar condicionado
(Tipo split)
Installatiehandleiding
Airconditioner
(Gesplitst type)
Εγχειρίδιο εγκατάστασης
Κλιματιστικό
(Τύπου Split)
Руководство по установке
Кондиционер воздуха
(сплит-система)
Montaj Kılavuzu
Klima
(Split tip)
English
1
Français
24
Deutsch
47
Italiano
70
(Tipo split)
Español
93
Português
116
Nederlands
139
Ελληνικά
162
Русский
185
Türkçe
208

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RBC-TRP100E

  • Page 1: Installation Manual

    AIR CONDITIONER (SPLIT TYPE) Installation manual Branch kit 1:3 Model name: RBC-TRP100E Installation manual English Air conditioner (Split type) Manuel d’installation Français Climatiseur (Type split) Installationshandbuch Deutsch Klimagerät (Split-typ) Manuale di installazione Italiano Condizionatore d’aria (Tipo split) Manual de instalación Español...
  • Page 2: Table Of Contents

    Branch Kit 1:3 Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the indoor unit. • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone...
  • Page 3: Precautions For Safety

    Branch Kit 1:3 PRECAUTIONS FOR SAFETY The three indoor units of TOSHIBA simultaneous triple packaged air conditioning system are the same units. Set and install the header and follower units taking the installation site into consideration. (Be certain to use the new refrigerant R410A in the indoor units.) The indoor unit connected to the remote controller will be the header...
  • Page 4 Branch Kit 1:3 • Install the air conditioner securely in a location where the base can sustain the weight adequately. • Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
  • Page 5 Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it. • The three indoor units of TOSHIBA simultaneous triple packaged air conditioning system are the same units. •...
  • Page 6: Component

    Branch Kit 1:3 COMPONENT The following parts are supplied as accessories of the branch pipes. Check them when opening the carton box. Distributor Part name Quantity Liquid side Gas side Different-size joint Ø12.7 → Ø9.5 Ø9.5 Liquid pipe Ø9.5 → Ø6.4 Ø15.9 Ø9.5 Ø25.4 →...
  • Page 7: Refrigerant Piping

    Branch Kit 1:3 REFRIGERANT PIPING Tolerance of pipe length and Height difference <RAV-SM1603AT(Z)(ZG)-E> Indoor unit A Indoor unit B Indoor unit C Branch pipe Branch pipe Branch pipe Distributor Main pipe Total length (L + a, L + b, L + c) 50 m Pipe length Branch pipe length (a, b, c)
  • Page 8 Branch Kit 1:3 <RAV-SM2244AT, SM2804AT series> Indoor unit A Indoor unit B Indoor unit C Branch pipe Branch pipe Branch pipe Distributor Main pipe Total length (L + a, L + b, L + c) 70 m Pipe length Branch pipe length (a, b, c) 20 m (one way) Maximum difference between indoor units...
  • Page 9: Piping Materials And Sizes

    Branch Kit 1:3 Piping materials and sizes <RAV-SM1603AT(Z)(ZG)-E> Use copper tube of Copper and copper alloy seamless pipes and tubes, with 40 mg/10 m or less in the amount of oil stuck on inner walls of pipe and 0.8 mm in pipe wall thickness for diameters 6.4, 9.5 and 12.7 mm and 1.0 mm, for diameter 15.9 mm.
  • Page 10: Air Purging

    Branch Kit 1:3 Distributor Now the refrigerant pipe is installed using distributor supplied as accessory. • Bend and adjust the refrigerant piping so that the distributor and pipe after branching become horizontal. • Fix the distributor onto a wall in a ceiling or onto a column. •...
  • Page 11: Additional Refrigerant Amount

    Branch Kit 1:3 Additional Refrigerant Amount <RAV-SM1603AT(Z)(ZG)-E> Indoor unit A Indoor unit B Indoor unit C Branch pipe Branch pipe Branch pipe Distributor Main pipe Formula for Calculating Additional Refrigerant Amount Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg) + Branch piping additional refrigerant amount (kg)
  • Page 12 Branch Kit 1:3 <RAV-SM2244AT, SM2804AT series> Indoor unit A Indoor unit B Indoor unit C Branch pipe Branch pipe Branch pipe Distributor Main pipe Formula for Calculating Additional Refrigerant Amount Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg) + Branch piping additional refrigerant amount (kg)
  • Page 13: Wiring

    Branch Kit 1:3 Gas Leak Test • Use a leak detector manufactured specially for the HFC refrigerant (R410A, R134a, etc.) when testing R410A. The sensitivity of leak detectors for previous HCFC refrigerants (such as R22) lowers to about 1/40 when used with HFC refrigerants and these detectors cannot be used. WIRING 1.
  • Page 14: Wiring Diagram

    Branch Kit 1:3 Wiring Diagram Remote Controller Header Follower Follower Indoor Indoor Indoor Unit Unit Unit Outdoor Unit L1 L2 L3 Power supply Power supply <RAV-SM1603AT-E> <RAV-SM2244AT, SM2804AT series> REQUIREMENT • The remote controller wiring has no polarity. Connections to terminals A and B of an indoor unit may be replaced with each other.
  • Page 15 Branch Kit 1:3 <RAV-SM1603AT(Z)(ZG)-E> WARNING For simultaneous triple systems, perform the following to conform to EMC standards. 1. Be sure to use shield wire for remote controller wiring. 2. Connect earth wire independently to each indoor unit. 3. Attach the ferrite core (white) supplied with the outdoor unit to indoor/outdoor connecting wires.
  • Page 16 Branch Kit 1:3 <2. Attaching the clamp filter> CN301 CN300 Fan motor lead wire (Lower side) Banding band Clamp filter Attach the clamp filter supplied with the outdoor unit to the lower outdoor fan motor lead wire. • Make sure that the claw of the clamp filter is securely locked. •...
  • Page 17 Branch Kit 1:3 <RAV-SM2244AT, SM2804AT series> Indoor/outdoor Power supply wire connecting wire Earth screw Earth screw Cord clamp Cord clamp Clamp filter Cord clamp Cord clamp (accessory) WARNING Be sure to attach the provided clamp filter to the power supply wire in order to conform to EMC standards.
  • Page 18 Branch Kit 1:3 NOTE When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power was on. However, it is not a trouble. Automatic address While automatic addressing, the operation can not be performed on the remote controller. •...
  • Page 19 Branch Kit 1:3 In case of group control in single system Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit (Max. 8 units) Remote Finish of address setup by power-ON controller •...
  • Page 20 Branch Kit 1:3 (Example) Group control for complex system Procedure Line <Single <Twin example a system <Triple system> system> system> Outdoor Outdoor Outdoor unit unit unit Indoor No. Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit (Example of Remote controller random...
  • Page 21 Branch Kit 1:3 Procedure example Procedure Every pushing button, the indoor Manual address setup procedure unit No. in the group control is displayed in While the operation stops, change the order. Select the indoor unit of which setup setup. (Be sure to stop the operation of the is changed.
  • Page 22 Branch Kit 1:3 Address change check Before change: Indoor unit No. before setup change is displayed. [3-3-1] → After change: [2-2-2] Pushing button clears the contents of which setup was changed. Indoor unit No. before setup change is displayed. Procedure 1.
  • Page 23 Branch Kit 1:3 To recognize the position of the Procedure corresponding indoor unit though In the group control, every pushing button, the indoor unit No. in the group the indoor unit No. is known control is displayed in order. Check the position during operation stop. At this time, the position of the indoor unit (Be sure to stop operation of the unit.) can be confirmed because only fan and...
  • Page 24: Piping Heat Insulation

    Branch Kit 1:3 PIPING HEAT INSULATION Heat insulation was produced locally. Be certain to heat insulate the piping both on the liquid and gas sides. • Use heat insulating materials for piping higher than 120 degree in heat resistance. Example: EPT - Ethylene, propylene, terpolymer •...
  • Page 25 EH99862001-...

Table of Contents