Toshiba RBC-TRP100E Installation Manual page 8

Hide thumbs Also See for RBC-TRP100E:
Table of Contents

Advertisement

Branch Kit 1:3
<RAV-SM2244AT, SM2804AT series>
Indoor unit C
Pipe length
(one way)
Refrigerant
pipe
specifications
Height
difference
Number of bent portions
CAUTION
When planning a layout for Units A, B and C, comply with the following:
1. The lengths after branching ("a" and "b", "b" and "c", "a" and "c") should be equal if
feasible. Install Units A, B and C so that the difference of the branching lengths becomes
less than 10 m if the lengths cannot be equal due to the branch pipe position.
2. Install Units A, B and C on the same level. If Units A, B and C cannot be installed on the
same level, the difference in level should be limited to 0.5 m or less.
EN
Indoor unit B
Branch pipe
c
L
Main pipe
Total length (L + a, L + b, L + c)
Branch pipe length (a, b, c)
Maximum difference between indoor units
Between indoor units (Δh)
Between indoor
unit and outdoor
unit
Branch pipe
b
Branch pipe
a
Distributor
(|a - b|, |b - c|, |c - a|)
When outdoor unit is higher (H)
When outdoor unit is lower (H)
7
Indoor unit A
10 or less
H
70 m
20 m
10 m
0.5 m
30 m
30 m