WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM
Unit will not run
Condenser fan runs, compressor
doesn't
Insufficient cooling
Compressor short cycles
Registers sweat
High head-low vapor pressures
High head-high or normal vapor
pressure - Cooling mode
High head-high or normal vapor
pressure - Heating mode
Low head-high vapor pressures
Low vapor - cool compressor -
iced evaporator coil
High vapor pressure
Fluctuating head & vapor
pressures
Gurgle or pulsing noise at
expansion device or liquid line
TROUBLE SHOOTING CHART
POSSIBLE CAUSE
• Power off or loose electrical connection
• Thermostat out of calibration-set too high
• Defective contactor
• Blown fuses
• Transformer defective
• High pressure control open (if provided)
• Interconnecting low voltage wiring damaged
• Run capacitor defective (single phase only)
• Loose connection
• Compressor stuck, grounded or open motor winding
open internal overload.
• Low voltage condition
• Improperly sized unit
• Improper airflow
• Incorrect refrigerant charge
• Air, non-condensibles or moisture in system
• Incorrect voltage
• Incorrect voltage
• Defective overload protector
• Refrigerant undercharge
• Low evaporator airflow
• Restriction in liquid line, expansion device or filter drier
• Flow check piston size too small
• Incorrect capillary tubes
• TXV does not open
• Dirty condenser coil
• Refrigerant overcharge
• Condenser fan not running
• Air or non-condensibles in system
• Low air flow - condenser coil
• Refrigerant overcharge
• Air or non-condensibles in system
• Dirty condenser coil
• Defective Compressor valves
• Low evaporator airflow
• Operating below 65°F outdoors
• Moisture in system
• TXV limiting refrigerant flow
• Excessive load
• Defective compressor
• TXV hunting
• Air or non-condensibles in system
• Air or non-condensibles in system
REMEDY
Check for correct voltage at compressor contactor in control
box
Reset
Check for 24 volts at contactor coil - replace if contacts are
open
Replace fuses
Check wiring-replace transformer
Reset-also see high head pressure remedy-
Replace thermostat wiring
Replace
Check for correct voltage at compressor -
check & tighten all connections
Wait at least 2 hours for overload to reset.
If still open, replace the compressor.
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Recalculate load
Check - should be approximately 400 CFM per ton.
Charge per procedure attached to unit service panel.
Recover refrigerant, evacuate & recharge, add filter drier
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
Replace - check for correct voltage
Add refrigerant
Increase speed of blower or reduce restriction - replace air
filter
Remove or replace defective component
Change to correct size piston
Change coil assembly
Replace TXV
Clean coil
Correct system charge
Repair or replace
Recover refrigerant, evacuate & recharge
Check filters - correct to speed
Correct system charge
Recover refrigerant, evacuate & recharge
Check filter - clean coil
Replace compressor
Increase speed of blower or reduce restriction - replace air
filter
Add Low Ambient Kit
Recover refrigerant - evacuate & recharge - add filter drier
Replace TXV
Recheck load calculation
Replace
Check TXV bulb clamp - check air distribution on coil - replace
TXV
Recover refrigerant, evacuate & recharge
Recover refrigerant, evacuate & recharge
19