Both versions are delivered with an integrated backup heater for
additional heating capacity during cold outdoor temperatures. The
backup heater also serves as a backup in case of malfunctioning of
the unit and for freeze protection of the outside water piping during
winter time. The backup heater factory set capacity is 6 kW, however,
depending on the installation, the installer can limit the backup heater
capacity to 3 kW. The backup heater capacity decision is a mode
based on the equilibrium temperature, see scheme below.
P
H
3
4
Heat pump capacity
1
Required heating capacity (site dependent)
2
Additional heating capacity provided by the backup heater
3
Equilibrium temperature (can be set through the user interface,
4
refer to "Field settings" on page 25)
Ambient (outdoor) temperature
T
A
Heating capacity
P
H
Domestic hot water tank EKHW* (option)
An optional EKHW* domestic hot water tank with integrated
3 kW electrical booster heater can be connected to the unit. The
domestic hot water tank is available in two sizes: 50 and
80 gallons (200 and 300 litre).
Room thermostat (option)
An optional room thermostat EKRTWA can be connected to the
unit.
Solar kit for domestic hot water tank (option)
An optional solar kit EKSOLHW can be connected to the unit.
Contact your dealer for more allowed solar kits.
Remote alarm kit (option)
Digital I/O PCB kit (option)
An optional EKRP1HB digital I/O PCB can be connected to the
indoor unit and allows:
■ remote alarm output
■ heating/cooling ON/OFF output
■ bivalent operation (permission signal for the auxiliary boiler)
Refer to the operation manual of the indoor unit and to the
installation manual of the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for
connecting this PCB to the unit.
To obtain more information concerning these option kits, please refer
to dedicated installation manuals of the kits.
Installation manual
2
Operation range
Heating mode
DB
35 95
0
1
–20
2
A
B
T
A
(*)
Connection to a benefit kWh rate power supply
This equipment allows for connection to benefit kWh rate power
supply delivery systems. Full control of the unit will remain possible
only in case the benefit kWh rate power supply is of the type that
power supply is not interrupted. Refer to "Connection to a benefit
kWh rate power supply" on page 21 for more details.

Scope of this manual

This installation manual describes the procedures for installing and
connecting all EDL and EBL outdoor unit models.
Model identification
EDL
A
CCESSORIES

Accessories supplied with the unit

A
DB
32
( )
–4
41
59 7277
104
131
5
15 2225
40
55
Outdoor temperature
Leaving water temperature
No heat pump operation, back up heater only
The models have a freeze prevention function using the pump and
back up heater to keep the water system safe from freezing in all
conditions.
In case accidental or intentional power shutdown is likely to happen
we recommend to use glycol. (Refer to Caution: "Use of glycol" on
page 16)
Q
036
BA
6
VJU
Backup heater capacity (kW)
Model changes
Indication of heating capacity (kBtu/h)
Refrigerant R410A
EDL = Monoblock outdoor heating only
EBL = Monoblock outdoor heat pump
(a) For exact values, refer to "Technical specifications" on page 40.
1
2
1x
1x
Installation manual
1
Operation manual
2
Wiring diagram sticker (inside unit cover doors 1 and 2)
3
User interface kit
4
(digital remote controller, 4 fixing screws and 2 plugs)
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
Cooling mode
A
46 115
10
50
*
B
B
41
72
5
22
Power supply:
2~, 208 V/230 V
(a)