Test Run And Final Check; Automatic Test Run; Test Run Operation (Manual); Maintenance And Service - Daikin EDLQ036BA6VJU1 Installation Manual

Unit for air to water heat pump system
Hide thumbs Also See for EDLQ036BA6VJU1:
Table of Contents

Advertisement

T
RUN AND FINAL CHECK
EST
The installer is obliged to verify correct operation of unit after
installation.
Final check
Before switching on the unit, read following recommendations:
■ When the complete installation and all necessary settings have
been carried out, close all front panels of the unit and refit the
unit cover.
The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.
Note that during the first running period of the unit,
NOTE
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.

Automatic test run

When the unit is put into operation (by pressing the
the first time, the system will automatically perform a test run in
cooling mode. The test run will take up to 3 minutes, during which no
specific indication is given on the user interface.
During the automatic test run, it is important to ensure that the water
temperature does not drop below 50°F (10°C), which might activate
the freeze-up protection and thereby prevent the test run to finish.
Should the water temperature drop below 50°F (10°C), press the
h/c button so the h icon is displayed. This will activate the backup
heater during the automatic test run and raise the water temperature
sufficiently.
If the automatic test run has ended successfully, the system will
automatically resume normal operation.
If there are misconnections or malfunctions, an error code will be
displayed on the user interface. To resolve the error codes, see "Error
codes" on page 39.
When the unit is put into pump down operation, the
NOTE
automatic test run flag will be cleared. The next time
the system is put into operation, the automatic test run
will be executed again.
After finishing automatic test run or power ON/OFF, the
compressor will operate in the selected operation
mode and continue for certain time (set point on the
remote controller is overruled during this operation).

Test run operation (manual)

If required, the installer can perform a manual test run operation at
any time to check correct operation of heating, cooling and domestic
water heating.
Procedure
Push the z button 4 times so the t icon will be displayed.
1
Depending on the unit model, heating operation, cooling
2
operation or both must be tested as follows (when no action is
performed, the user interface will return to normal mode after 10
seconds or by pressing the z button once):
To test the heating operation push the h/c button so the h
·
icon is displayed. To start the test run operation press the
y button.
To test the cooling operation push the h/c button so the c
·
icon is displayed. To start the test run operation press the
y button.
To test the domestic water heating operation push the v
·
button. The test run operation will start without pressing the
y button.
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56182-1
The test run operation will end automatically after 30 minutes or
3
when reaching the set temperature. The test run operation can
be stopped manually by pressing the z button once. If there are
misconnections or malfunctions, an error code will be displayed
on the user interface. Otherwise, the user interface will return to
normal operation.
To resolve the error codes, see "Error codes" on page 39.
4
NOTE
NOTE
M
AINTENANCE
In order to ensure optimal availability of the unit, a number of checks
and inspections on the unit and the field wiring have to be carried out
at regular intervals.
This maintenance has to be carried out by your local Daikin
y
button) for
technician.
The described checks must be executed at least once a year by
qualified personnel.
Water pressure
1
Check if the water pressure is above 14.5 psi (1 bar). If
necessary add water.
Water filter
2
Clean the water filter.
Water pressure relief valve
3
Check for correct operation of the pressure relief valve by
turning the red knob on the valve counter-clockwise:
■ If you do not hear a clacking sound, contact your local dealer.
■ In case the water keeps running out of the unit, close both
the water inlet and outlet shut-off valves first and then contact
your local dealer.
Pressure relief valve hose
4
Check that the pressure relief valve hose is positioned
appropriately to drain the water.
To display the last resolved error code, push the z
button 1 time. Push the z button again 4 times to
return to normal mode.
It is not possible to perform a test run if a forced
operation from the unit is in progress. Should forced
operation be started during a test run, the test run will
be aborted.
AND SERVICE
DANGER: ELECTRIC SHOCK
Before carrying out any maintenance or repair activity,
always switch off the circuit breaker on the supply
panel, remove the fuses (or switch off the circuit
breakers) or open protection devices of the unit.
Make sure that before starting any maintenance or
repair activity, also the power supply to the outdoor
unit is switched off.
Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.
The heater of the compressor may operate even in
stop mode.
Please note that some sections of the electric
component box are hot.
Make sure you do not touch a conductive section.
Do not rinse the unit. This may cause electric shocks
or fire.
When service panels are removed, live parts can be
easily touched by accident.
Never leave the unit unattended during installation or
servicing when service panel is removed.
Installation manual
37