Toshiba BMS-SM1280HTLE Service Manual page 30

Smart manager
Hide thumbs Also See for BMS-SM1280HTLE:
Table of Contents

Advertisement

12-2.Operation Check
Complete the test run of air conditioners before operation check.
No.
Item
1
Start-up check
2
Check for electric
energy meter input
3
Check for fire alarm
input
4
Logon
5
Check at the time of
air conditioner
setting change
6
Check air conditioner
status display
Details
• Turn on the all air conditioners.
• Turn on the all interfaces.
• Turn on Smart Manager and check that the LCD
displays all the air conditioners where the
intensive management addresses are set.
• Check that the interfaces LEDs properly illuminate
or blink.
Energy Monitoring Relay
LED1 (Red) illuminates
I/F
LED2 (Green) blinking
Digital Input / Output
LED1 (Red) illuminates
Relay I/F
LED2 (Green) blinking
Check for electric energy meter pulse input
Check for fire alarm signals input; Check for electric
lock signals input
From the client PC browser, access Smart Manager
to display the logon screen.
In the logon screen, enter a user name and a
password to log on.
Factory setting: user name (TCC), password (TCC)
(*) Logon in not available immediately after the start-
up. Wait for approx. 5 minutes and enter the
information to log on.
Start or stop the air conditioner from the client PC to
check that the air conditioner operates accordingly.
Change the operation status or setting status using
the air conditioner remote controller to check that
the client PC monitor screen properly displays the
status.
For further details, refer to the Installation
manual of each device.
For further details, refer to the Network
Configuration Guide of Smart Manager.
For further details, refer to the Owner's
manual of the Smart Manager.
30
Procedure

Advertisement

Table of Contents
loading

Table of Contents