8-3. Digital Input / Output Relay Interface (BMS-IFDD03E)
The following settings are necessary to use Digital Input / Output Relay Interfaces.
Address setting
RS-485 terminator resistor
setting
12V
GND
DO1
DO2
DO3
DO4
SW1 Address set switch
When two or more Digital Input / Output Relay Interfaces are used, set a different address for each unit
to avoid address duplication.
Set SW7 as "120 ohm" on a Digital Input / Output Relay Interface with address SW1=1, when the Digital
Input / Output Relay Interface is used in a system without Energy Monitoring Relay Interface. Set SW7
as "Open" on the other interfaces.
LED4
LED2
SW7
LED5
LED3
LED1
SW3
SW2
SW1
1 2 3 4
SW6
SW4
LED9
LED7
LED8
LED6
SW1
Address set switch
1-8
0, 9-F
SW2
Operating mode set switch (0 usually)
SW3
Test switch (all OFF usually)
SW4
Test switch
SW6
Reset switch
RS-485 terminator resistor select switch
ON
SW7
120 ohm
LED1
Power indicator
LED2
RS-485 communication status indicator
LED3
Not used
LED4
Test indicator
LED5
Test indicator
LED6 -LED9
Digital output indicator
25
Address
Not used
ON
Open

Advertisement