OPERATING PROCEDURE
6. Removing the vane motor
(1) Remove the air intake.
(2) Remove the left side panel.
(3) Remove the relay connector of vane motor.
(4) Remove the electrical box.
(5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place
them in the proper position so that the wires are not pinched
by other parts.
7. Removing the indoor coil thermistor
(1) Remove the air intake grill.
(2) Remove the right side panel.
(3) Remove the relay connector of the indoor coil thermistor.
(4) Remove the screw, and remove the check panel.
(5) Extract the indoor coil thermistor from the holder.
<Caution for the installation>
There is a possibility for the short circuit when connector gets
wet by water through the thermistor lead wire.
Therefore, lead wire of the indoor coil thermistor should be
traped as shown in the picture.
8. Removing the under panel
(1) Remove the air intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Unscrew the screws of the under panel, then remove the
lower panel.
wWeight of the lower panel : approx. 2kg
PHOTOS & ILLUSTRATIONS
Photo 4
Relay connector of
the vane motor
Photo 5
Screw
Left side
panel
Photo 6
Hold
Indoor coil thermistor
Screws
Photo 7
62
Screw
Vane motor
Relay connector of
Check
the pipe thermistor
panel
Trap
Under panel