7-6. HOW TO CHECK THE PARTS
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
Parts name
Room temperature
Disconnect the connector then measure the resistance with a tester.
thermistor
(TH1)
(At the ambient temperature 10:~30:)
Pipe temperature
thermistor
(TH2)
Fan motor (MF)
Measure the resistance between the terminals with a tester.
Relay connector
(Winding temperature 20:)
1
Red
1
White
2
2
3
Black
3
Protector
OFF : 130i 5:
ON : 80i 20:
Vane motor (MV)
4
Orange
5
M
Red
2
Pink
Yellow Brown Blue
3 6 1
4
Pink
M
2
Orange
5
Red
Yellow
Blue
3
1
Drain-up (DP)
Measure the resistance between the terminals with a tester.
mechanism (Option)
(Winding temperature 20:)
Gray
1
3
Gray
Normal
4.3k"~9.6k"
Open or short
Motor terminal
or
2
Relay connector
Red–Black
70.6"
White–Black
69.6"
Connector
Brown–Yellow
Brown–Blue
186~214"
Red–Orange
Red–Pink
Normal
Connector
4, 5, 6
Brown–Yellow
Brown–Blue
140~160"
Red–Orange
Red–Pink
Normal
195"
Open or short
Check points
Abnormal
(Refer to the next page for a detail.)
Normal
2.5, 3
45.0"
44.8"
Normal
2
2.5, 3
140~160"
Abnormal
Open or short
Abnormal
35
4
5,6
43.7"
20.4"
55.3"
20.7"
Abnormal
Open or short
Abnormal
Open or short