12.5 Quiet operation (Cooling Mode/Cooling area of Dry Mode)

Purpose
To provide quiet cooling operation compare to normal operation.
o
Control condition

Quiet operation start condition

o
When "POWERFUL/QUIET" button at remote control is pressed twice.
POWERFUL/QUIET LED illuminates.

Quiet operation stop condition

o
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer "off" activates.
AUTO COMFORT button is pressed.
ECONAVI button is pressed.
Mild Dry Cooling button is pressed.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer "on" activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control contents
Fan speed is changed from normal setting to quiet setting of respective fan speed.
o
This is to reduce sound of Hi, Me, Lo for 3dB (some models more than 3dB).
Fan speed for quiet operation is reduced from setting fan speed.
o
12.6 Quiet operation (Heating)
Purpose
To provide quiet heating operation compare to normal operation.
o
Control condition
Quiet operation start condition
o
When "POWERFUL/QUIET" button at remote control is pressed.
POWERFUL/QUIET LED illuminates.
Quiet operation stop condition
o
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer "off" activates.
AUTO COMFORT button is pressed.
ECONAVI button is pressed.
Mild Dry Cooling button is pressed.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except
fan mode only.
During quiet operation, if timer "on" activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
1
2
90
70
CS-E18, 21NK CS-XE18, 21NK
72
3
4
80
100
5
110