13-EN
Air to Air Heat Exchanger with DX Coil Unit
Model No.
A
MMD-VNK502HEXE, VN502HEXE
1,690
MMD-VNK802HEXE, VN802HEXE
1,739
MMD-VNK1002HEXE, VN1002HEXE
1,739
MMD-VNK1002HEXE2, VN1002HEXE2
1,739
Model No.
G
MMD-VNK502HEXE, VN502HEXE
173
MMD-VNK802HEXE, VN802HEXE
198
MMD-VNK1002HEXE, VN1002HEXE
198
MMD-VNK1002HEXE2, VN1002HEXE2
198
Center of gravity
X
Model No.
X
MMD-VNK502HEXE
902
MMD-VNK802HEXE
901
MMD-VNK1002HEXE
900
MMD-VNK1002HEXE2
894
MMD-VN502HEXE
870
MMD-VN802HEXE
856
MMD-VN1002HEXE
853
MMD-VN1002HEXE2
858
Installation Manual
B
C
D
E
1140
1140
250
175
1189
1189
275
200
1189
1189
275
200
1189
1189
275
200
Diameter of
Duct
refrigerant
H
I
J
K
diameter
piping at the
gas side (L)
Ø195
Ø212
1601
1197
Ø200
Ø9.5
Ø245
Ø262
1650
1246
Ø250
Ø12.7
Ø245
Ø262
1650
1246
Ø250
Ø12.7
Ø245
Ø262
1650
1246
Ø250
Ø12.7
Y
Z
643
174
667
199
667
199
666
199
642
174
663
198
663
198
662
198
– 7 –
Air to Air Heat Exchanger with DX Coil Unit

Installing the indoor unit

Unit: mm
F
Attaching the duct connector
350
Attach 4 duct connectors to the unit using the six screws supplied for each connector.
400
400
400
Diameter of
refrigerant
piping at the
liquid side (M)
Ø6.4
Attaching the washers and nuts
Ø6.4
1
Ø6.4
Procure the hanging bolts, nuts, and washers locally.
Ø6.4
2
Attach the washers and nuts to the hanging bolt (M12) as shown in the figure on the right.
Z
Fixing the unit
1
Fit the hanging bracket on the hanging bolt, then adjust the position of the unit so that it is level.
2
Tighten the bolts securely using a double nut to prevent the bolts from becoming loose.
• If the bolts are not tightened securely, the unit will vibrate and an accident may occur.
• Tighten the bolts so that they can bear the weight of the unit.
3
Confirm that the unit is installed level.
• Confirm that the unit is installed level or is inclined within 1°(downward) against the drain outlet using a spirit
level.
• Do not set the unit inclined (upward) against the drain outlet; otherwise, water will leak from the unit.
Weight
Within 1°
91
111
112
114
84
100
101
103
CAUTION
To preventing vibration, use vibration proof hanging brackets (procured locally).
Duct connector
Screws
Hanging bolt
(M12)
Nut
Washer
Nut
Hanging bolt (Ø12)
Within 1°
Hanging bolt (Ø12)
Vibration-proof hanging
bracket
14-EN
Installation Manual
Nut
Washer
Washer
Nut
Hanging bracket
Vibration-
proof hanging
bracket

Advertisement

Table of Contents
loading

Table of Contents