Wiring Connection; Address Setting; Wiring The Indoor Unit - Toshiba MMD-VNK502HEXE Installation Manual

Air to air heat exchanger with dx coil unit
Hide thumbs Also See for MMD-VNK502HEXE:
Table of Contents

Advertisement

25-EN
Air to Air Heat Exchanger with DX Coil Unit

Wiring connection

NOTE
• When performing transition wiring for the remote controllers, polarity is not needed to be considered when connecting
wires to the terminal A and B on the indoor unit terminal block.
• Leave an extra length of 100mm for each wiring so that servicing can be performed more easily.
• Low voltage circuit is applied for the remote controller.
Perform wiring so that each wire corresponds with the proper terminal number; otherwise, an electrical fault may
occur.
Wiring in the electrical control box of the indoor unit
Fix the wires using a cord clamp. Do not stretch them tight for wiring.

Wiring the indoor unit

Connect the wire matching the terminal numbers.
Incorrect connection causes a trouble.
R
S
(L)
(N)
Earth wire
Power supply
wire
Installation Manual
Communication wire terminal block
Wiring between indoor and outdoor unit (U1, U2)
Wiring for the remote controller (A, B)
External output terminal block
Operation output
Common
External damper output (3-4)
Abnormal/Bypass mode output (3-5)
Humidistat terminal block
Earth screw
Power supply terminal block (R (L), S (N))
Cord clamp
Wiring for the
remote controller
Wiring between
indoor and outdoor
unit
Earth Screw
– 13 –
Air to Air Heat Exchanger with DX Coil Unit
Remote control wiring
Wiring diagram
Indoor unit remote
A
controller terminal
B
block
* Use a 0.5mm
2
to 2mm
2
wire.

Address setting

Refer to the Installation Manual of the outdoor unit for address setting.
* When the Air to Air Heat Exchanger with DX Coil Unit system linked with indoor air conditioners is used, set the
Air to Air Heat Exchanger with DX Coil Unit as "Follower", referring to "Setting the address manually using the
remote controller" in the Installation Manual of the outdoor unit.
Switching between Extra High and High
When switching to Extra High, connect the black lead wire (Extra High) to the connector.
* The Orange lead wire (High) is connected as factory default.
* Connect the black lead wire both to the air supplying motor (white connector) and the air exhausting motor (red
connector).
* Refer to "Connection diagram" for the connection method.
Remote control wire
(locally procured)
Remote control unit
A
B
Remote controller terminal block
Air supply
Air exhaust
(white connector)
(red connector)
26-EN
Installation Manual