Electrical Service Guide; Extension Cord Data - Miller Spectrum 625 X-TREME Owner's Manual

Air plasma cutter
Hide thumbs Also See for Spectrum 625 X-TREME:
Table of Contents

Advertisement

4-7. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
NOTICE − INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of
input power at rated frequency(+10%) and voltage (+10%). Phase to ground voltage shall not exceed +10% of rated input voltage. Do not use a genera-
tor with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
Input Voltage (V)
Input Amperes (A) At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

4-8. Extension Cord Data

.
When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
Input Power
Phase
Input Voltage
208 V
1
230 V
1
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose − no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
OM-237 974 Page 14
.
A complete Parts List is available at www.MillerWelds.com
1
2
Time-Delay Fuses
3
Normal Operating Fuses
4
4
Circuit Breaker Rating
Hertz
Time-Delay
60
Normal Operating
Time-Delay
60
Normal Operating
Fuse Size Or
Conductor Size
2
40 A
3
50 A
2
35 A
3
45 A
60 Hz Single
Phase
208
33
40
50
10
80
(24)
10
Max. Cord Length
10 AWG
80 ft (24 m)
10 AWG
98 ft (30 m)
230
30
35
45
10
98
(30)
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spectrumice-40t torchIce-40t

Table of Contents