Mitsubishi Electric FR-F720-00046 Installation Manuallines page 18

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

Name
Parameters
PU communication
122
check time interval
PU communication
123
waiting time setting
PU communication
124
CR/LF selection
Terminal 2
125
frequency setting
gain frequency
Terminal 4
126
frequency setting
gain frequency
PID control automatic
127
switchover frequency
128
PID action selection
PID proportional
129
band
130
PID integral time
131
PID upper limit
132
PID lower limit
133
PID action set point
134
PID differential time
Electronic bypass
135
sequence selection
MC switchover
136
interlock time
Waiting time at a
137
start
Bypass selection at
138
a fault
Automatic
switchover
139
frequency from
inverter to bypass
operation
Backlash
140
acceleration
stopping frequency
Backlash
141
acceleration
stopping time
Backlash
142
deceleration
stopping frequency
Backlash
143
deceleration
stopping time
Speed setting
144
switchover
PU display language
145
selection
Stall prevention
148
level at 0V input.
Stall prevention
149
level at 10V input.
*1
Setting of "9" can be made for the FR-F720-03160 (FR-F740-01800) or more.
Setting
Initial
Range
Value
0, 0.1 to 999.8s,
9999
9999
0 to 150ms,
9999
9999
0, 1, 2
1
0 to 400Hz
60Hz
0 to 400Hz
60Hz
0 to 400Hz,
9999
9999
10, 11, 20, 21,
50, 51, 60, 61,
10
110, 111, 120,
121
0.1 to 1000%,
100%
9999
0.1 to 3600s,
1s
9999
0 to 100%,
9999
9999
0 to 100%,
9999
9999
0 to 100%,
9999
9999
0.01 to 10.00s,
9999
9999
0, 1
0
0 to 100s
1s
0 to 100s
0.5s
0, 1
0
0 to 60Hz,
9999
9999
0 to 400Hz
1Hz
0 to 360s
0.5s
0 to 400Hz
1Hz
0 to 360s
0.5s
0, 2, 4, 6, 8,
10, 102, 104,
4
106, 108, 110
0 to 7
1
0 to 120%
110%
0 to 120%
120%
Name
Parameters
Output current
150
detection level
Output current
151
detection signal
delay time
Zero current
152
detection level
Zero current
153
detection time
Voltage reduction
selection during
154
stall prevention
operation
RT signal reflection
155
time selection
Stall prevention
156
operation selection
OL signal output
157
timer
AM terminal
158
function selection
Automatic
switchover
159
frequency range
from bypass to
inverter operation
User group read
160
selection
Frequency setting/
161
key lock operation
selection
Automatic restart after
162
instantaneous power
failure selection
First cushion time
163
for restart
First cushion
164
voltage for restart
Stall prevention
165
operation level for
restart
Output current
166
detection signal
retention time
Output current
167
detection operation
selection
168
Parameter for manufacturer setting.
Do not set.
169
Cumulative power
170
meter clear
Operation hour
171
meter clear
User group
172
registered display/
batch clear
User group
173
registration
174
User group clear
STF terminal
178
function selection
PARAMETER LIST
Setting
Initial
Range
Value
0 to 120%
110%
0 to 10s
0s
0 to 150%
5%
0 to 10s
0.5s
0, 1
1
0, 10
0
0 to 31, 100,
0
101
0 to 25s, 9999
0s
1 to 3, 5, 6,
8 to 14, 17, 21,
1
24, 50, 52, 53
*1
0 to 10Hz,
9999
9999
0, 1, 9999
0
0, 1, 10, 11
0
0, 1, 10, 11
0
0 to 20s
0s
0 to 100%
0%
0 to 120%
110%
0 to 10s, 9999
0.1s
0, 1, 10, 11
0
0, 10, 9999
9999
0, 9999
9999
9999, (0 to 16)
0
0 to 999, 9999
9999
0 to 999, 9999
9999
0 to 8, 10 to 12,
14, 16, 24, 25,
60
60, 62, 64 to 67,
70 to 72, 9999
15