How To Check The Components - Mitsubishi Electric PUHZ-RP3VHA Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-RP3VHA:
Table of Contents

Advertisement

HOW TO CHECK THE COMPONENTS

<Thermistor feature chart>
Low temperature thermistors
Outdoor pipe <liquid> temperature thermistor (TH3)
Outdoor condenser/evaporator temperature thermistor (TH6)
Outdoor outside temperature thermistor (TH7)
Thermistor R0 = 15k' ± 3%
B constant = 3480k' ± 2%
1
=15exp{3480( 273+t – 273 )}
R
t
0:
15k'
30:
10:
9.6k'
40:
20:
6.3k'
25:
5.2k'
Medium temperature thermistor
Heat sink temperature thermistor (TH8)
Thermistor R50 = 17k' ± 2%
B constant = 4150k' ± 3%
1
=17exp{4150( 273+t – 323 )}
R
t
0:
180k'
25:
50k'
50:
17k'
70:
8k'
90:
4k'
High temperature thermistor
Discharge temperature thermistor (TH4)
Thermistor R120 = 7.465k' ± 2%
B constant = 4057k' ± 2%
1
=7.465exp{4057( 273+t – 393 )}
R
t
20: 250k'
70:
30: 160k'
80:
40: 104k'
90:
50:
70k'
100: 13.0k'
60:
48k'
110:
1
4.3k'
3.0k'
1
1
34k'
24k'
17.5k'
9.8k'
50
40
30
20
10
0
-20 -10 0 10 20 30 40 50
Temperature (:)
200
150
100
50
0
25
Temperature (:)
500
400
300
200
100
0
25
Temperature (:)
40
50
75
100
125
50
75
100
120

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puhz-rp4vhaPuhz-rp5vhaPuhz-rp6vha