Vertical Concentric Flue Fitting Details Lbf81/121 - Lochinvar LBF81 Installation, Commissioning & Maintenance Instructions

High efficiency gas fired water heaters
Hide thumbs Also See for LBF81:
Table of Contents

Advertisement

9.3.2

VERTICAL CONCENTRIC FLUE FITTING DETAILS LBF81/121

FIGURE 8.3
Kit Part Number
ASKITSV
1000mm Vertical Concentric Flue Kit
Kit Components
1
38mm Clamp With Gasket (Not Visible)
2
3
4
38/60mm Extension Piece(38mm section not Visible)
5
6
38/100 – 1m Vertical Terminal
TABLE 8.3
1.
Determine the desired location for the flue terminal, taking into account minimum distances as detailed
in Figure 8.1, Table 8.1 and the relevant British Standards.
2.
Taking care to protect the appliance from debris and dust, drill a hole in the desired location. The
diameter of the hole should be no more than 10mm greater than the diameter of the air supply pipe of
the terminal.
NOTE:
The hole should be drilled from the outside to ensure that no damage is done to the roofing material.
Extra care should be taken to ensure that the hole is drilled vertically.
3.
Install the roof flashing and secure as appropriate.
4.
Carefully insert the roof terminal through the roof flashing and hole in the roof.
NOTE:
When inserting the roof terminal do not support or turn the terminal using the cap.
5.
Ensure the terminal is vertical using a spirit level.
6.
Fit the support bracket around the terminal and secure using appropriate fixings. Do not tighten the
support bracket.
7.
Fit the 90° concentric bend to the flue hood by first sliding the 38mm clamp and gasket over the exhaust
connection and then pushing the elbow on to the 60mm air connection.
8.
If an additional length of flue pipe is required to connect to the vertical terminal this should be measured,
cut accordingly and fitted using the 38mm and 60mm clamps and gaskets included with the additional
length.
9.
If no additional components are required measure and cut the terminal accordingly and insert into the
100/60mm duct adaptor (item 5 in Figure 8.3) followed by the 38/60mm extension piece (item 4 in
Figure 8.3) and then finally fit to the 90° bend.
10. With all components in position, tighten any support brackets used.
VERTICAL CONCENTRIC FLUE KIT FOR LBF81/121
Description
60mm Clamp With Gasket
38/60 90° Concentric Bend
100/60 Duct Adaptor
VERTICAL CONCENTRIC FLUE KIT AND COMPONENTS LBF-81/121
Additional Components
ASPC100
38/60 Extension (Adjustable 1000mm)
Description
23