3.4. Terminal Block Explanation

Tower model
OUTPUT
G2
N22
L22
N21
N22, L22, N21, L23, L21: UPS OUTPUT
G2
: OUTPUT EARTH GROUND
6000C or RT6K model
TB1
TB2
INPUT
BYPASS
(DIM TYPE ONLY)
INPUT
L23
L21
G1
N1
L12
L11
UTILITY
INPUT
L11-N1: BYPASS INPUT
(DIM TYPE ONLY)
L12-N1: UTILITY INPUT
G1
: INPUT EARTH GROUND
RT10K model
TB1
TB2
192408SN0000400
16
L11-N1、B-N1: the terminal for Bypass Input to provide the power source when
the UPS is working under bypass mode.
L12-N1、R-S-T-N1: the terminal for Utility Input to provide the power source
when the UPS is working under Utility mode.
G1: the terminal for UPS Input Ground.
L21、L23、N21、L22、N22: the terminals for UPS Output.
G2: the terminal for UPS Output Ground.
Remarks:
1. The maximum current for each terminal is 30Arms
10Kva.
2. If the UPS is DIM(Dual Input) type whose Utility and Bypass Sources are the
same, L11 and L12 would have to be shorted for 1-phase input model, and
short B and R for 3-phase input model.
3. If the UPS is SIM(Single Input) type, only AC source can be supplied to UPS
from L12-N1 terminal for 1-phase input model and R-S-T-N1 terminal for 3-
phase input model.
4. When the Isolation transformer is NOT installed into the tower type UPS, the
UPS output terminals will be L22-N22..
5. When the Isolation transformer is installed into the tower type UPS:
a. For 100/110/115/120Vac system, you may connect as shown in below.
N22
L22
110Vac
6KVA (Max)
b. For 200/100Vac, 220/110Vac, 230V/115Vac, or 240/120Vac, or
240/208/120Vac system,
You may connect as shown in below.
208Vac
N22
L22
120Vac
3KVA (Max)
for 6Kva, 50Arms for
N21
L23
L21
6KVA (Max)
N21
L23
L21
120Vac
3KVA (Max)
240Vac
6KVA (Max)
17