1. Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1.
1-5. Maintenance, Service And Faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
2. Installation And Setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1. Rear Panel View 800/1.1K/1.5K/2K IEC Type 2.5K/3K IEC Type 800/1.1K/1.5K/2K Schuko Type 2.5K/3K Schuko Type 800/1.1K/1.5K/2K India Type...
2-2. Install The UPS For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first. Step 1 Step 2 Step 3 Remove front panel. Connect the AC input and Put the front panel back to the re-connect battery wires.
Page 7
Step 3: Communication connection Communication ports: USB port RS-232 port Intelligent slot To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
Step 7: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period. Step 8: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
2-5 Battery Kit Assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it. 2-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart.
Page 10
6-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells. below chart.
3. Operations 3-1. Button Operation Button Function Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system.
Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minute Warning & Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in details in 3-5 section.
3-4. LCD Display Wordings Index Abbreviation Display content Meaning Enable Disable Escape Temperature Charger Rack display Tower display Site Fault 3-5. UPS Setting Parameters 2 There are two parameters to set up the UPS. Parameter 1: It’s for program alternatives. There are 4 programs to set up: output voltage setting, , programmable outlets enable/disable, Parameters 1...
Page 14
03: Programmable outlets setting Interface Setting Setting the backup time limits in minutes from 0-999 for programmable outlets which connect to non-critical devices on battery mode. 04: LCD display direction setting Interface Setting RAC: the LCD display is horizontal. TOE: the LCD display is vertical.
Step 4: Press the “Up“ button (ON/MUTE) again to switch to "03" of program list. Then press “Enter“ button for setting programmable outlet time. Push “Up” button to change the value of backup time according your demand. Then press “Enter” to confirm the setting. Step 5: Press “Up“...
Operating mode Description LCD display Standby mode UPS is powered off and no output supply power, but still can charge batteries. 3-7. Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail Inverter output short Bus over Battery voltage too high Bus under...
4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even The AC input power is not Check if input power cord though the mains is normal. connected well.
Page 18
Symptom Possible cause Remedy Fault code is shown as 1, 2, 3, 4, A UPS internal fault has Contact your dealer 11, 12, 13 and 41 on LCD display occurred. and alarm is continuously sounding. Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value...
5. Storage and Maintenance 5-1. Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
6. Specifications MODEL 1.1K(L) 1.5K 2K(L) 2.5K 3K(L) 800 VA / 1100 VA / 1500 VA / 2000 VA / 2500 VA / 3000 VA / CAPACITY 640 W 880 W 1200 W 1600 W 2000 W 2400 W INPUT Acceptable Voltage Range 81-145 VAC or 162-290 VAC Frequency Range...