Bundled Software Installation Guide; Hardware Installation; Software Installation - Orvaldi MSII RT 6-10KVA User Manual

Parallel redundancy on-line ups
Table of Contents

Advertisement

Situation
Check Items
UPS Red Fault
Check the error code
LED lights up
shown on the LCD screen
1. Er05,
&
2. Er06, Er10, Er12 Er28 &
3. EPO
4. Er11, Er33
5. Er14
6. Er15
7. Er16, Er27
8. Er21
9. Er24
10. other error code
UPS fails to
offer battery
backup or its
back up time is
shorter than its
calculation.
UPS locks
itself and it can
not be turned
off.
Solution
1. Check to see if the battery connection is
properly done, then re-charge the
batteries for 8 hours to see whether the
UPS may backup normally; otherwise,
consult your local distributor right away.
2. If the CB3 is tripped, please turn off the
UPS completely and keep the CAM
switch at position INV before pressing
CB3. Then remove some uncritical load
at the UPS output end. If any damage of
the coating of AC power cord, please
replace a new one.
3. Remove the short circuit occurred at the
EPO terminal.
4. Remove the objects blocked onto the
ventilation holes.
5. Check the cooling fans on rear panel
are working normally.
6. Make sure the UPS is operated
normally. If it is on CVCF mode, you
have to turn off and turn on the UPS
again.
7. All of parameters except ID Number in
the parallel UPS must be same. Please
refer chapter 3.5.5 to set them again
8. Reconnect the RJ-45 wire or set a UPS
with ID=1.
9. When the UPS is on CVCF mode, it is
prohibited to have bypass input. You
have to turn off the UPS and bypass
input and re-start the UPS.
10. Consult your local distributor for help.
If the backup time is still too short after 8
hours of charge, please contact your local
distributor for battery replacement.
Please refer to chapter 3.5.6 to trouble
shoot the problem; otherwise, consult your
local distributor for help.
32

5. Bundled Software Installation Guide

5.1. Hardware Installation

1. Connect the male connector of RS232 cable to the UPS communication
port.
2. Connect the female connector of the RS232 cable to a dedicated RS232
port of the computer.
3. For optional interface cards, you may refer to Chapter 6 for installation.

5.2. Software Installation

Please refer to the user's manual of the software for installation.