1. Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1.
1-5. Maintenance, service and faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
2. Installation and setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
6. Emergency power off function connector (EPO) 7. USB communication port 8. RS-232 communication port 9. SNMP intelligent slot 10. External battery connection (only available for L model) 11. Input terminal 12. Output circuit breaker 2-2. Rack-Mounted the UPS This UPS can be mounted in the 19” rack chassis. Please follow below steps to position this UPS.
Page 7
AC input in 3K model for safety operation. Step 3: UPS output connection For socket-type outputs, there two kinds of outputs: programmable outlets and general outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
Step 7: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period. Step 8: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
Remove the top cover of After replacing the batteries, Re-connect the battery wires. battery box and replace the put the battery box back to inside batteries. original location and screw it tightly. Step 7 Put the front panel back to the unit. 2-5 Battery kit assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS.
Page 10
3-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells and insert one below chart.
Page 11
6-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells. below chart.
3. Operations 3-1. Button operation Button Function Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system.
Page 13
Display Function Backup time information Indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hours, M: minute, S: second Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in details in 3-5 section.
3-3. Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously sounding Bypass Mode Sounding every 10 seconds 3-4. LCD display wordings index Abbreviation Display content Meaning Enable Disable Escape High loss Low loss Battery...
Page 15
01: Output voltage setting Interface Setting Parameter 3: Output voltage For 200/208/220/230/240 VAC models, you may choose the following output voltage: 200: presents output voltage is 200Vac 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac 240: presents output voltage is 240Vac For 100/110/150/120/127 VAC models, you may choose...
Page 16
For 100/110/115/120/127 VAC models, the setting range in parameter 3 is from +3V to +12V of the nominal voltage. LLS: Low loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V of the nominal voltage. For 100/110/115/120/127 VAC models, the setting voltage in parameter 3 is from -3V to -12V of the nominal voltage.
10: Backup time setting for outlets Interface Setting Parameter 3: Set up backup time on battery mode for general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode. 0: When setting as “0”, the backup time will be only 10 seconds.
Standby mode UPS is powered off and no output supply power, but still can charge batteries. 3-7. Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail Inverter voltage Low Bus over Inverter output short Bus under Battery voltage too high Bus unbalance...
4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even The AC input power is not Check if input power cord though the mains is normal. connected well.
Page 20
Symptom Possible cause Remedy Fault code is shown as 14 and the The UPS shut down Check output wiring and if automatically because connected devices are in icon is lighting on LCD short circuit occurs on the short circuit status. display and alarm is continuously UPS output.
5. Storage and Maintenance Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.