Piping Connection Size - LG AMNH076LQL0 Service Manual

Multi type
Hide thumbs Also See for AMNH076LQL0:
Table of Contents

Advertisement

2.3 Piping connection size

Liquid
Gas
A
A6UW406FA0
Y-Branch
2.4 Necessity of a trap
Since there is fear of the oil held inside the riser piping
flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of
deterioration of oil return, it will be necessary to pro-
vide a trap at an appropriate place in the riser gas pip-
ing.
A
mm
Ø 9.52
mm
Ø19.05
A
A
B
B
Adjust to indoor unit
piping size
BD Unit
B
B
In case more then 5m
• Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
Installation
B
B
B
CAUTION
Service Manual 77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents