Napoleon Arlington GDS20N Installation And Operation Instructions Manual page 12

Natural gas/propane
Table of Contents

Advertisement

12
when (H
) > (V
)
T
T
Simple venting configuration (only one 45º and 90° elbow)
See graph to determine the re-
quired vertical rise V
for the re-
T
quired horizontal run H
REQUIRED
VERTICAL
RISE IN
INCHES (V
)
T
HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)
The shaded area within the lines represents acceptable
values for H
and V
.
T
T
For vent configurations requiring more than one 45º and
90° elbow the following formulas apply:
Formula 1: H
< 4.2 V
T
Formula 2: H
+ V
< 24.75 feet
T
T
W415-0496 / B / 08.10.05
NorthlineExpress.com
HORIZONTAL TERMINATION
FIGURE 7
.
T
T
http://www.northlineexpress.com
Example 2:
90°
FIGURE 8
H
1
45°
90°
V
1
V
= 4 ft
1
V
= 1.5 ft
2
V
= V
+ V
= 4 ft + 1.5 ft = 5.5 ft
T
1
2
H
= 2 ft
1
H
= 1 ft
2
H
= 1 ft
3
H
= 1.5 ft
4
H
= H
+ H
+ H
+ H
R
1
2
3
H
= .03(one 45º elbow + three 90º elbow -135º)
O
=.03(315-135)=5.4ft
H
= H
+ H
= 5.5 +5.4 = 10.9 ft
T
R
O
H
+ V
= 10.9 + 5.5 = 16.4 ft
T
T
Formula 1: H
< 4.2 V
T
4.2 V
T
10.9 < 16.8
Formula 2: H
+ V
< 24.75 feet
T
T
16.4 < 24.75
Since both formulas are met, this vent configuration is ac-
ceptable.
90°
H
H
V
3
4
2
H
2
= 2 + 1 + 1 + 1. 5 = 5.5 ft
4
T
= 4.2 x 5.5 = 23.1 ft
Toll-Free 1-866-667-8454

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arlington gds20p

Table of Contents