Troubleshooting Guide - Napoleon Arlington GDS20N Installation And Operation Instructions Manual

Natural gas/propane
Table of Contents

Advertisement

24
B
EFORE ATTEMPTING TO TROUBLESHOOT
SYMPTOM
Pilot will not light.
No spark at pilot burner
No gas at the pilot burner
Out of propane gas.
System is not correctly purged.
Pilot goes out when
the gas knob is re-
Out of propane gas
leased.
Pilot flame is not large enough
Pilot flame is not engulfing the
thermocouple.
Thermocouple shorting.
Faultly thermocouple.
Faulty valve.
Pilot burning; no
Main burner orifice is plugged.
gas
to
main
Faulty thermopile.
burner; gas knob
Faulty themostat or switch.
is on 'HI'; wall
switch / thermostat
is on.
Faulty valve.
Gas piping is undersized.
Pilot goes out while
standing;
Main
burner is in 'OFF'
position.
Main burner goes
Pilot flame is not large enough
out; pilot stays on.
or not engulfing the thermo-
pile.
Thermopile shorting
Remote wall switch wire is too
long, too much resistance in
the system
Faulty thermostat or switch
W415-0496 / B / 08.10.05
NorthlineExpress.com
TROUBLE SHOOTING GUIDE
,
PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED
PROBLEM
Spark gap is incorrect
http://www.northlineexpress.com
TEST SOLUTION
- check if pilot can be lit by a match
- check that the wire is connected to the push button ignitor.
- check if the push button ignitor needs tightening.
- replace the wire if the wire insulation is broken or frayed.
- replace the electrode if the ceramic insulator is cracked or
broken.
- spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.)
from the electrode tip and the pilot burner. To ensure proper
electrode location, tighten securing nut (finger tight plus 1/4
turn).
- check that the manual valve is turned on.
- check the pilot orifice for blockage.
- replace the valve.
- call the gas distributor.
- fill the tank.
- purge the gas line with the stove door open.
- fill the tank.
- turn up the pilot flame.
- turn up pilot flame.
- replace pilot assembly.
- loosen and tighten thermocouple.
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- replace.
- replace.
- remove stoppage in orifice.
- replace.
- connect a jumper wire across the wall switch terminals; if
main burner lights, replace thermostat.
- disconnect switch wires from the valve & connect a jumper
wire across terminals 1 & 3; if the main burner lights, check the
wires for defects and / or replace wires.
- disconnect the pilot light wires from the valve and connect a
jumper wire across terminals 1 & 3; if the main burner lights,
check the wires for defects and / or replace wires.
- replace.
- turn on all gas appliances and see if pilot flame flutters,
diminishes or extinguishes, especially when main burner ig-
nites. Monitor supply pressure.
- check if supply piping size is to code. Correct all undersized
piping.
- turn up pilot flame.
- replace pilot assembly.
- clean thermopile and thermopile connection to valve.
- shorten wire to correct length or wire gauge.
- replace
.