Maintenance Checklist - Roberts Gorden CoRayVac CRV-B-2 Installation, Operation & Service Manual

Custom-engineered, low-intensity infrared heating systems
Hide thumbs Also See for CoRayVac CRV-B-2:
Table of Contents

Advertisement

CRV-S
I
, O
ERIES
NSTALLATION
PERATION AND
inspection of the heater.
For best performance, the gas, electrical, thermostat
connections, tubing, venting, suspensions and
overall heater condition should be thoroughly
inspected.
NOTE: Gas flow and burner ignition are among the
first things that should be inspected.
Please see Page 72, Section 16.5 for suggested
items to inspect.

16.5 Maintenance Checklist

Installation Code and Annual Inspections:
The Vicinity of the Heater
Vehicles and Other
Objects
Reflector
Vent Pipe
Outside Air Inlet
Tubes
72 of 83
S
M
ERVICE
ANUAL
Do not store or use flammable objects, liquids or vapors near the heating sys-
tem. Immediately remove these items if they are present.
See Page 5, Section 3.
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 24, Figure 7 .4.3.
Clean outside surface with a damp cloth.
Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe or gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
See Page 35, Section 9.
Inlet must be intact. Look for obstructions, cracks on the pipe or gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 19, Figure 14 through Page 21, Section 7 .2.1.
Make sure there is no dirt, sagging, bending or distortion.
Clean or replace as required.
All installation and service of ROBERTS GORDON
equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
conform to all requirements set forth in the
®
ROBERTS GORDON
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON
equipment and perform service where necessary,
using only replacement parts sold and supplied by
Roberts-Gordon LLC.
manuals and all applicable
®
®

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents