Custom-engineered, low-intensity infrared heating systems (94 pages)
Summary of Contents for Roberts Gorden DUAL AIR DAT100
Page 1
® Heating and Cooling Units Installation, Commissioning, Operation & Service Manual DAT75 DAT90 DAT100 DAT115 Installer Please take the time to read and understand these instructions prior to any installation. Installer must give a copy of this manual to the owner. Owner Keep this manual in a safe place in order to provide your serviceman with necessary information.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 1: HEATER SAFETY Your Safety is Important to Us! 2.1 Clearances to Combustibles This symbol is used throughout the In all situations, clearances to combustibles must be manual to notify you of possible fire, maintained.
SECTION 3: C RITICAL ONSIDERATIONS SECTION 3: CRITICAL CONSIDERATIONS 3.1 Basic Information 3.7 Electrical Supply The CTUD heater that forms the heating section of A permanent 400v 3ø 50Hz electrical supply is required at the main electrical terminals. The heater ®...
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL Figure 2: Installation Clearances and Clearances to Combustibles **80 cm is necessary to ® * Free blowing DualAir units may be mounted at service heater. a higher level if destratification fans and/or turn down nozzles are installed.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 4.2 General Technical Data Table Model Fan Data 2.88 Designed Air Flow # with Clean Filters /sec 1.66 2.60 Min Air Flow at Coil /sec 3.71 5.34 Max Air Flow at Coil /sec Fan Unit 457-486 Double Inlet Belt Drive...
SECTION 4: S PECIFICATIONS 4.3 Technical Data Table - Heater Section Appliance Category II 2H/L 3B/P Model Heat Input Gross Calorific Value Btu/h x 1000 Heat Input Net Calorific Value Btu/h x 1000 Approximate Max Heat Output Btu/h x 1000 66.5 77.7 83.3...
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL ® 4.4 DualAir Performance Data - Graph of Air Flows v Static Pressure 4.4.1 DAT75 and 90 (2.2 kW or 4 kW motor) 4.4.2 DAT100 and 115 (4 kW motor)
SECTION 5: H EATER NSTALLATION SECTION 5: HEATER INSTALLATION 5.3 Shelf Mounting and Suspension 5.1 General ® DualAir units are designed for installation above 2.5 m. When connected to duct delivery systems any suitable location will be acceptable. ® For floor mounting, the DualAir unit may stand directly on its base.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 6: FLUE INSTALLATION 6.1 Flue Installation Figure 4: Flue and Roof Detail The flue must terminate outside of the building. Flues and air intakes must be fully sealed and correctly sized for the model.
SECTION 6: F NSTALLATION 5. Refit the air intake spigot to the flexible hose re- using the hose clamp and to the upper panel using the original screws. 6. Align the flues’ inner and outer spigots and attach through the holes in the upper panel re- using the original screws.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL Figure 7: Vertical and Horizontal Flue Termination - Type B Appliance Figure 8: Vertical and Horizontal Flue Termination - Type C & C Appliances...
SECTION 7: A UPPLY SECTION 7: AIR SUPPLY 7.1 Room Sealed Installation 7.3 Building Ventilation When installed as a room sealed heater, the air for Where ventilation is required, air must be taken from combustion is drawn in from outside the building. It an outside point where it is not likely to be is important to ensure that there is adequate contaminated or obstructed.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 8: OPTIONAL HEATER CONFIGURATIONS 8.1 Distribution Duct The duct must be designed as described on Page ® DualAir units are designed to be connected to 14, Section 8.1 and Figure 10 to ensure that there is distribution and air inlet ducting.
SECTION 9: G IPING SECTION 9: GAS PIPING 9.1 Connections Connect the heater to the gas supply ensuring that the final connections are as follows: • The gas supply pipe is adequately sized to carry the total volume of gas for the complete installation.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 10: WIRING AND ELECTRICAL INFORMATION 10.1 Electrical Supply cooling temperature control. See Page 20, Section 10.6. All heater models need a constant 400 V 50 Hz 3 ø To operate the modulating gas burner, a further supply connected to terminals L , N &...
SECTION 10: W IRING AND LECTRICAL NFORMATION 10.3 DAT Main Circuit Board Terminal Identification Terminal Relay/Function Operation Number Input for Remote Fan Opera- Optional - Main Fan Runs from 1 Input or Output External Fan Control tion Output for Fan Operation External Control Monitor 230 V 50 Hz supply of external...
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 10.4 DAT Wiring Diagram NOTE: For external fan wiring, See Page 20, Section 10.6. If any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°...
SECTION 11: C OMMISSIONING SECTION 11: COMMISSIONING Gas Fired Heater 11.1.2 Electrical Checks Installation, service, commissioning and annual 1. Check that all site wiring is connected in inspection of the heater must be done by a accordance with the appropriate wiring dia- contractor qualified in the installation and service of grams on Page 17 , Section 10.3 through Page gas-fired heating equipment.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL Figure 12: Automatic Burner Control Box Sequence If at any stage the flame fails, the control will go to "lockout". The red light will illuminate and the control must be manually reset before further start attempt. Figure 13: Modureg Gas Valve...
SECTION 11: C OMMISSIONING 11.4.2 Commissioning the Gas Valves sure must be corrected before completing the commission. ® All DualAir units are fitted with fully modulating burner operation. The Honeywell automatic gas 2. Release the moving shaft and observe that the valves are fitted with the Honeywell Modureg burner pressure returns to the minimum setting.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL water collection and a shortened heat exchanger life. Pressure Switch The pressure switch is factory pre-set for each model and is not adjustable. ® 11.6 Turning Off the DualAir Unit Set the external controls to the off position and the main burner will stop.
SECTION 12: U NSTRUCTIONS SECTION 12: USER INSTRUCTIONS 12.1 User Instructions 12.3 Common User Controls 12.3.1 Combination Fan/Limit Thermostat ® The DualAir units are fully automatic and operate from the external controls fitted on site. The Combination Fan/Limit Thermostat is located inside the access door at the top of the heater.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL ® Do not operate the DualAir unit without filters as the cooling coil may become blocked and impossible to clean. 12.5 Heating Section Lighting Instructions 12.5.1 To Turn On Heater 1.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 13: SERVICING 13.1 Servicing Instructions to ensure that adequate air flow. The cooling equipment will automatically turn off ® After commissioning, the DualAir unit will require should the air flow drop to a preset low value even maintenance to be carried out annually.
SECTION 13: S ERVICING 13.5 Gas Control Valve Maintenance No regular maintenance is required on these devices. To change gas control valves, See Page 36, Step 16.1 and Page 40, Section 16.5. Do not repair or disassemble on site. Replace faulty gas valves with genuine ®...
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 14: CONVERSION BETWEEN GASES 14.1 General Conversion between gasses will require a change of burner injectors and the gas valve re-commissioning to the new conditions. 14.2 Burner Conversion Conversion of the burner assembly from one gas to the other is the same for all types of heaters.
SECTION 15: T ROUBLESHOOTING SECTION 15: TROUBLESHOOTING 15.1 General ® For your safety and optimum heater performance use only ROBERTS GORDON replacement parts. Conduct Commissioning procedure as shown on Page 21, Section 11...
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 15.2 Troubleshooting For Automatic Ignition Burner Systems There are two burner controls used. Honeywell S4563C and S4565C. They both have similar operating sequences. To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe.
SECTION 15: T ROUBLESHOOTING 15.3 Troubleshooting for Flame Supervision System NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 15.4 Troubleshooting for Solenoid Valves 15.5 Troubleshooting for Main Fan ® For your safety and optimum heater performance use only ROBERTS GORDON replacement parts. Conduct Commissioning procedure as shown on Page 21, Section 11...
SECTION 15: T ROUBLESHOOTING 15.6 Troubleshooting for Fan Contactor ® For your safety and optimum heater performance use only ROBERTS GORDON replacement parts. Conduct Commissioning procedure as on Page 21, Section 11...
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL SECTION 16: REMOVAL AND REPLACEMENT PARTS Figure 17: Standard Regulator Removal See warnings and notes on Page 28, Section 13 before removing or replacing parts. Burner Components All serviceable burner parts are accessed by the door on the side of the heater.
SECTION 16: R EMOVAL AND EPLACEMENT ARTS 16.2 Burner Compartment The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight. 16.2.1 Burner Injectors Ensure gas tight fitting of injectors.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 16.3 Ignition Electrode and Flame Probe. To replace the ignition electrode or flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.
SECTION 16: R EMOVAL AND EPLACEMENT ARTS 16.4 Flue Fan Remove screws securing outlet flange to the flue adapter. Remove screws securing flue fan mounting plate to vent box Remove screws securing mounting plate to fan. Refit in reverse. Use new gaskets. Ensure sealed joints.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 16.5 Heater Pressure Switch Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are colour coded for each pressure setting. Carry out a commission after working on or changing a pressure switch.
SECTION 16: R EMOVAL AND EPLACEMENT ARTS 16.6 Cooling Coil Safety Devices 16.6.1 Cooling Coil Frost Thermostat Coil Pressure Switch (Normally open contact) used to prove adequate air The sensing element for this device is inserted into flow for safe operation of cooling coil. the pocket of the cooling coil situated through the access hole in the coil cover.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL 16.7 Ignition Control IT IS IMPORTANT THAT ONLY THE CORRECT IGNITION CONTROL SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS. 16.7.1 S4563C This control is mounted at the electrical mounting plate.
SECTION 16: R EMOVAL AND EPLACEMENT ARTS 16.8.1 Fan Removal and Replacement Description Part Number Torin Fan DDC 270-270 A047 Torin Fan DDC 241-241 A049 1. Remove motor leaving the pulley in place. 3. Fit a new thermostat ensuring that the correct See Page 42, Section 16.8.
® EATING AND COOLING NITS NSTALLATION PERATION AND ERVICE ANUAL Figure 19: Combination Fan/Limit Thermostat Dial Set Point 3 Limit Temp. Set Point 2 Fan On Push Screwdriver in and hold to release Set Point 1 Fan Off Push in Lock Wire to Controlled Equipment Fan Terminals Limit Stat...
Page 52
Roberts-Gordon, LLC Roberts-Gordon Europe Limited...