Figure 28: Gas Connection With Flexible Gas Hose - Roberts Gorden CoRayVac CRV-B-2 Installation, Operation & Service Manual

Custom-engineered, low-intensity infrared heating systems
Hide thumbs Also See for CoRayVac CRV-B-2:
Table of Contents

Advertisement

CRV-S
I
, O
ERIES
NSTALLATION
PERATION AND

FIGURE 28: Gas Connection with Flexible Gas Hose

Shut-Off Valve (included with gas hose) must
be parallel to burner gas inlet. The 3" (8 cm)
displacement shown is for the cold condition.
This displacement may reduce when the
system is fired.
3" (8 cm)
max. displacement
12"
(30 cm)
Flexible Gas Hose
36" (91 cm) length
Heater Movement
Heater Movement
Description
1/2" Flexible Stainless Steel Gas Hose (US Models)
3/4" Flexible Stainless Steel Gas Hose (US Models)
1/2" Rubber (Type 1) Gas Hose (Canadian Models)
3/4" Rubber (Type 1) Gas Hose (Canadian Models)
48 of 83
S
M
ERVICE
ANUAL
CORRECT POSITIONS
Side View
Heater Movement
INCORRECT POSITIONS (WRONG INSTALLATION)
CAUTION
Product Damage Hazard
Hold gas nipple securely with pipe wrench
when attaching gas hose.
Failure to follow these instructions can result
in product damage.
(as shown left)
Horizontal
End View
Heater Movement
Heater Movement
Part Number
91412200
91412204
91412206
91412207
Vertical
45°
Alternate
positions
okay

Hide quick links: