PERATION AND
Step 8.8 Classic Cast-Iron Components
Special Tube and Reflector Hanger
Schedule 40 Steel Pipe
Cast-Iron Combustion Chamber
with Schedule 40 Steel Pipe
The total weight of each burner and
combustion chamber is 40.25 lbs (18 kg).
4" Schedule 40 pipe weighs 10.9 lbs.
(5 kg) per foot.
Coupling
4" Tube
Cast-Iron Combustion Chamber with
Standard 4" O.D. Infrared Tubing
The total weight of each burner and
combustion chamber is 40.25 lbs (18 kg).
4" O.D. 16 Ga. tubing weighs 2.8 lbs.
(1.3 kg) per foot.
34 of 83
S
M
ERVICE
ANUAL
WARNING
Severe Injury Hazard
Hang heater with materials with a minimum
working load of 750 lbs. (340 kg).
Use special tube and reflector hangers when
suspending the schedule 40 steel pipe system.
Schedule 40 steel pipe is heavy and will fall if
not supported properly.
Distance between supports must be 7' (2.13 m)
or less.
Failure to follow these instructions can result
in death, injury or property damage.
7' (2.13 m) Maximum
ROBERTS-GORDON
CORAYVAC
Cast-Iron Combustion
Chamber
ROBERTS-GORDON
Cast-Iron Adapter
Turnbuckle
Hang cast-iron combustion chamber with a turnbuckle
(spring clips will not fit around cast-iron hanging loop).
®
Cast-Iron Adapter
®
Classic
®
Description
Special Tube & Reflector Hanger
Turnbuckle
Cast-Iron Combustion Chamber
Cast-Iron Adapter
Coupling
End Vent
Clips
End Vent Plate for
End Burner Only
End Vent
Clips
End Vent Plate for
End Burner Only
Part Number
02790300
91903201
02721200-1P
02722100
01312700

Hide quick links: