Pentair Fleck 5600SXT Downflow Service Manual page 19

Hide thumbs Also See for Fleck 5600SXT Downflow:
Table of Contents

Advertisement

TROUBLESHOOTING continued
Error Codes
NOTE: Error codes appear on the In Service display.
Error Code
Error Type
0
Cam Sense
Error
1
Cycle Step
Error
2
Regen
Failure
3
Memory
Error
UD
Upper Drive
Sync
Cause
The valve drive took longer than
6 minutes to advance to the next
regeneration position
The control experienced an
unexpected cycle input
The system has not regenerated
for more than 99 days (or 7 days
if the Control Type has been set to
Day-of-Week)
Control board memory failure
Power failure install programming
change
Reset and Recovery
Unplug the unit and examine the powerhead. Verify that all cam switches are
connected to the circuit board and functioning properly. Verify that the motor
and drive train components are in good condition and assembled properly.
Check the valve and verify that the piston travels freely. Replace/reassemble
the various components as necessary.
Plug the unit back in and observe its behavior. The unit should cycle to
the next valve position and stop. If the error re-occurs, unplug the unit and
contact technical support.
Unplug the unit and examine the powerhead. Verify that all cam switches
are connected to the circuit board and functioning properly. Enter Master
Programming mode and verify that the valve type and system type are set
correctly with regard to the unit itself.
Step the unit through a manual regeneration and verify that it functions
correctly. If the error re-occurs unplug the unit and contact technical support.
Perform a Manual Regeneration to reset the error code.
If the system is metered, verify that it is measuring flow by running service
water and watching for the flow indicator on the display. If the unit does not
measure flow, verify that the meter cable is connected properly and that the
meter is functioning properly.
Enter a Master Programming Mode and verify that the unit is configured
properly. As appropriate for the valve configuration, check that the correct
system capacity has been selected, that the day override is set properly,
and that meter is identified correctly. If the unit is configured as a Day-of-
Week system, verify that at least one day is set ON. Correct the settings as
necessary.
Perform a Master Reset and reconfigure the system via Master Programming
Mode. After reconfiguring the system, step the valve through a manual
regeneration. If the error re-occurs unplug the unit and contact technical
support.
Valve will automatically recover.
Fleck 5600SXT Downflow JE11 • 19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents