Kohler 40EFOZ Operation Manual page 61

Marine generator sets
Hide thumbs Also See for 40EFOZ:
Table of Contents

Advertisement

Terminal
1
Ground—emergency stop relay (K4)—connect
emergency stop across terminals TB1-1 and
1A *
1A
Emergency stop relay (K4) coil; negative
side—connect emergency stop across
terminals TB1-1 and 1A *
2
Ground terminal
Overcrank (OC) indicator [
12
Auxiliary (AUX) indicator [
26
32
Common fault/prealarm line 1—A/V alarm or
common fault relay activated by OC, 12; AUX,
26; LWT, 35; HET, 36; LOP, 38; OS, 39; PHET,
40; PLOP, 41; and LF, 63 faults
32A
Common fault/prealarm line 2—A/V alarm or
common fault relay activated by AUX, 26;
HET, 36; LOP, 38; OS, 39; and E-Stop, 48
faults
35
Low water temperature (LWT) indicator
High engine temperature (HET) indicator [
36
Low oil pressure (LOP) indicator [
38
Overspeed (OS) indicator [
39
40
Prealarm high engine temperature (PHET)
indicator [
41
Prealarm low oil pressure (PLOP)
indicator [
42A
Battery voltage (fuse #1 protected)—
accessory power supply; customer may also
provide separate accessory power source
Emergency stop (ES) indicator [
48
56
Air damper (AD) indicator, if equipped;
standard on all 200--2000 kW Detroit
Diesel-powered models
System ready indicator [
60
61
Battery charger fault—connect battery charger
alarm contact to TB1-61 to activate fault lamp
(active low) (if used)
62
Low battery volts—connect battery charger
alarm contact to TB1-62 to activate fault lamp
(active low) (if used)
63
Low fuel (LF) fault—connect fuel level sensor
to TB1-63 to activate fault lamp (active low) (if
used)
70C
Generator in cool down mode signal
70R
Generator in running mode signal
Not in auto indicator [
80
* Connect jumper across terminals 1 and 1A if emergency stop
switch is not used.
[ Use a remote annunciator and/or A/V alarm kit as an indicator
with a dry contact kit connected to controller terminal strip TB1.
Note:
Not all terminals are used for all generator sets (see
appropriate wiring diagrams for specific generator set model).
Figure 5-20 Controller TB1 Terminal Strip
(Decision-Makert 3+ Controller)
TP-6109 6/03
Purpose
Terminal
1P
Prime power operation
2P
Prime power operation
Remote start ground—connect transfer
3
switch or remote start switch to TB2--3 and
TB2--4
3P
Prime power operation
Remote start—connect transfer switch or
4
remote start switch to TB2--3 and TB2--4
4P
Prime power operation
Crank mode selection (open: cyclic crank,
ground: continuous crank); connect TB2--9
9
to TB2--9A for continuous cranking; leave
TB2--9 open cyclic cranking; see starting
instructions in Section 2, Operation.
9A
Crank mode ground
Note: To use prime power mode—place jumpers across TB2-1P to
TB2-2P, TB2-3P to TB2-4P, and TB2-3 to TB2-4. To deactivate
prime power mode—remove jumpers across TB2-1P to TB2-2P,
TB2-3P to TB2-4P, and TB2-3 to TB2-4.
Figure 5-21 Controller TB2 Terminal Strip
(Decision-Makert 3+ Controller)
Purpose
Section 5 Wiring Diagrams
51