Auxiliary Fault Lamp Conditions - Kohler 40EFOZ Operation Manual

Marine generator sets
Hide thumbs Also See for 40EFOZ:
Table of Contents

Advertisement

2.6.3

Auxiliary Fault Lamp Conditions

The following descriptions define the possible auxiliary
fault lamp conditions.
Flashing Lamp Conditions
No AC Output. The auxiliary lamp flashes immediately
if the controller senses no AC output while the generator
set runs (except during the first 10 seconds after
startup). The flashing stops and the light goes out when
the controller senses AC output. The controller requires
no manual reset.
Low Battery Voltage. The auxiliary lamp flashes if the
battery power was reconnected or was low and then
restored while the generator set master switch was in
the RUN or AUTO position. A possible cause is a
temporary low battery condition when the battery is
weak or undersized for the application. To clear the low
battery voltage condition, place the generator set
master switch in the OFF/RESET position.
Continuous-On Lamp Conditions
Emergency Stop Switch Energized. Upon activation
of the emergency stop switch, if equipped, the auxiliary
lamp lights and the generator set shuts down
immediately.
TP-6109 6/03
Emergency Stop Switch Reset.
optional emergency stop switch while the generator set
master switch is in the AUTO or RUN position causes
the auxiliary lamp to light. Place the generator set
master switch in the OFF/RESET position to clear the
auxiliary lamp ON condition.
Note: Auxiliary Delay Shutdown. The auxiliary lamp
lights and the engine shuts down 5 seconds after
the high oil temperature (P1-13) or auxiliary delay
shutdown (P1-15) fault, if equipped, occurs.
Auxiliary Delay Shutdown is inhibited during the
first 30 seconds after crank disconnect.
Note: Overvoltage Shutdown. If a generator set is
equipped with this kit, the auxiliary lamp lights
and the engine shuts down immediately when an
overvoltage condition occurs.
Note: Auxiliary Immediate Shutdown. The auxiliary
lamp lights and the engine shuts down
immediately
when
sensing
devices
immediate shutdown ports (P1-17 and P1-18)
activate them.
Resetting the
any
customer-supplied
connected
to
auxiliary
x:op:005:004
Section 2 Operation
11