Precision Cooling for Business- - Critical Continuity Liebert HPC- -S 006- -022 Air Cooled Chillers with Scroll compressor/s PRODUCT DOCUMENTATION...
Page 2
Liebert HPC-- S 006-- 022 Liebert HPC---S 006---022 Liebert HPC-S 006---022 is the new Emerson Network Power product line of air-cooled water chillers, from 60 to 220 kW, designed to combine the best performance in terms of efficiency and reliability with the lowest impact on the environment and to offer a flexible solution for each different application requirement of this product.
2006/42/EC; 2004/108/EC; 2006/95/EC 97/23/EC. Units are supplied complete with a test certificate and conformity declaration and control component list. Liebert HPC- -S 006- -022 units are CE marked as they comply with European directives concerning mechanical, electrical, electromagnetic and pressure equipment safety.
High outdoor temperature The oversizing of heat exchangers and the wide operating range of the scroll compressors permit the use of Liebert HPC ---S 006 ---022 units in high temperature environments as well, up to 46° C at 100% full load.
Page 5
Freecooling Module The “Freecooling” execution allows Liebert HPC ---S 006 ---022 to take advantage of low outdoor air tem- peratures in the water cooling process in order to save energy, by avoiding compressors running.
Page 6
Through @connectivity the information on the cooling needs of the air conditioners is available to the Liebert HPC ---S 006 ---022 units, that will manage their resources (compressors and free cooling) in the most efficient way in order to save addition- al energy.
Page 7
To add the @connectivity to your system, it is simply necessary: To build up Hironet connection between the room units and the Liebert HPC ---S 006 ---022 units. The network can be only 1 (if the distance and the number of units allow this) or it can be split in several net- works.
---10 ---5 Ambient Temperature (_C) This diagram shows the average working limits of all the products family. Refer to table 3 for the working limits of each unit. 3 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 11
HP safety valves (each circuit) High pressure safety valve connection inch 3/4” G Low pressure switch barg (1) --- With nominal air flow; water outlet temperature 7° C; full load; R410A refrigerant. 3 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 12
HP safety valves (each circuit) High pressure safety valve connection inch 3/4” G Low pressure switch barg (1) --- With nominal air flow; mixture outlet temperature 10° C; full load; R410A refrigerant. 3 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
(2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 14
(2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 15
(2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 16
(2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 4 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 17
(3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 5 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 18
(3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 6 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 19
(3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 7 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 20
(3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 8 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
The units are designed for being used with refrigerant R410A. Compressor The Liebert HPC ---S 006 ---022 series is equipped with two hermetic, scroll compressors specifically de- signed for application in refrigeration systems. Tandem compressors consist of two compressors which can be equal or different size models; they offer advantages over single compressors with equivalent capacity such as: Efficient capacity control - through cycling one or two compressors.
Page 22
Evaporators Liebert HPC ---S 006 ---022 units are equipped with direct expansion, weld ---brazed plate type evaporat- ors, designed, constructed, tested (pressure test on both refrigerant and water sides) and documented to comply with PED 97/23/EC standards. The corrugation (typical angle) and the design of each plate have been thoroughly analyzed and thus optimized to better meet the physical features of the refrigerant (R410A) and provide for an optimal refrigerant distribution.
Page 23
Freecooling Execution Liebert HPC ---S 006 ---022 models in the ”Freecooling execution” are designed with an integrated free- cooling system consisting of: cooling coils with copper tubes and aluminium fins, mounted in vertical configuration;...
Page 24
Recirculating Pumps (Option) All the models of the Liebert HPC ---S 006 ---022 series can be equipped with one or two water circulating pumps, factory ---piped.
Page 25
The company is not responsible for damage due to incorrect or improper use of the product and it reserves the right to change technical specifications without any prior notice. 5 -- 5 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 26
The machine is supplied with a final test certificate and a declaration of conformity with the norms. All Liebert HPC ---S 006 ---022 units are ” ” marked. Accessories...
Page 27
CEA 210/5 FHE 40--- 160/40 FHE 40--- 200/55 210/4 370/5 40--- 160/30 Nominal Motor Power 1.50 1.85 3.00 4.00 5.50 Noise Level dB(A) (*) --- According to ISO 3744 5 -- 7 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
300 litres Other Accessories The following accessories can be installed as an option: Anti ---vibrating mounts (spring / rubber). Dee shackle UNI 1947. Coldfire IP40 remote box. Water filter. 5 -- 8 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Input for Remote on ---off and Volt---free contacts for simple remote monitoring of alarms and warn- ings are available. Up to 16 Liebert HPC ---S 006 ---022 units can be easily linked together on a network to provide teamwork mode, stand ---by operation and duty cycling without additional hardware. Reliability is not affected if there are problems on the data communication buses, because the units return auto- matically to the stand ---alone mode.
Page 30
The IS cards and other gateway represent the communication managers portfolio which allow the integ- ration of the Liebert HPC ---S 006 ---022 units into the most diffused Building Management Systems. The most diffused are: SNMP , HTTP , MODBUS and LONWORK.
1800 0,988 1,015 Unit performance reported in the tables are given for sea level conditions. For different altitude, performances should be corrected with the correction factors shown above. 7 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
94.0 CB0014 FB0014 94.5 CB0015 FB0015 94.5 CB0018 FB0018 96.0 CB0019 FB0019 96.5 CB0022 FB0022 97.0 Note: Sound power levels tolerance for each octave band: --- 0/+2 dB 8 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 33
97.5 CG0009 FG0009 97.5 CG0011 FG0011 97.5 CG0014 FG0014 99.0 CG0015 FG0015 99.0 CG0018 FG0018 99.0 Note: Sound power levels tolerance for each octave band: --- 0/+2 dB 8 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 34
Sound power levels tolerance for each octave band: --- 0/+2 dB In the ”G” version chiller, the characteristics of the ”EC” fans can achieve significant noise reductions according to their speed (RPM). 8 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
High head pressure pump --- Nominal power 1,85 High head pressure pump --- Max. current (1) --- Outdoor temperature 35° C; water inlet/outlet temperature 12/7° C; R410A refrigerant. 9 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 43
Minimum distance between 2 units from condensing coil side = 2 m. Do not obstruct the air exiting the fans for a minimum distance of 2.5 m. (*) Extraordinary maintenence area for unit with tank: 1000 mm. 10 -- 7 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
Page 51
De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is: Vaimistaja vakuuttaa täten, että tämä tuote täyättää seuraavien EU--- direktiivien vaatimukset: Since the Liebert HIROSS Company has a policy of continuous product improvement, it reserves the right to change design and Produsent erklærer herved at dette produktet er i samsvar med EU--- direktiver:...
Page 52
2008 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. Emerson Network Power...