Liebert HPC- -S
006- -022
Air Cooled Chillers with Scroll compressor/s
PRODUCT DOCUMENTATION
Precision Cooling for
Business- - Critical Continuity

Advertisement

Table of Contents
loading

Summary of Contents for Liebert HPC-S 006

  • Page 1 Precision Cooling for Business- - Critical Continuity Liebert HPC- -S 006- -022 Air Cooled Chillers with Scroll compressor/s PRODUCT DOCUMENTATION...
  • Page 2 Liebert HPC-- S 006-- 022 Liebert HPC---S 006---022 Liebert HPC-S 006---022 is the new Emerson Network Power product line of air-cooled water chillers, from 60 to 220 kW, designed to combine the best performance in terms of efficiency and reliability with the lowest impact on the environment and to offer a flexible solution for each different application requirement of this product.
  • Page 3: Table Of Contents

    2006/42/EC; 2004/108/EC; 2006/95/EC 97/23/EC. Units are supplied complete with a test certificate and conformity declaration and control component list. Liebert HPC- -S 006- -022 units are CE marked as they comply with European directives concerning mechanical, electrical, electromagnetic and pressure equipment safety.
  • Page 4: Liebert Hpc-- S

    High outdoor temperature The oversizing of heat exchangers and the wide operating range of the scroll compressors permit the use of Liebert HPC ---S 006 ---022 units in high temperature environments as well, up to 46° C at 100% full load.
  • Page 5 Freecooling Module The “Freecooling” execution allows Liebert HPC ---S 006 ---022 to take advantage of low outdoor air tem- peratures in the water cooling process in order to save energy, by avoiding compressors running.
  • Page 6 Through @connectivity the information on the cooling needs of the air conditioners is available to the Liebert HPC ---S 006 ---022 units, that will manage their resources (compressors and free cooling) in the most efficient way in order to save addition- al energy.
  • Page 7 To add the @connectivity to your system, it is simply necessary: To build up Hironet connection between the room units and the Liebert HPC ---S 006 ---022 units. The network can be only 1 (if the distance and the number of units allow this) or it can be split in several net- works.
  • Page 8: Model Number Description

    6 = Web card + Sitescan card 0 = None 7 = Modbus card + Sitescan card X = As specified 8 = Bacnet card (Bacnet or Modbus over IP) 2 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 9 15 = 1, then digit 12 = 2, 3, 4 or 5 if digit 15 = 2, then digit 12 = 1 if digit 10 = 2, then digit 15 = 1 or 2 2 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 10: Operating Range

    ---10 ---5 Ambient Temperature (_C) This diagram shows the average working limits of all the products family. Refer to table 3 for the working limits of each unit. 3 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 11 HP safety valves (each circuit) High pressure safety valve connection inch 3/4” G Low pressure switch barg (1) --- With nominal air flow; water outlet temperature 7° C; full load; R410A refrigerant. 3 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 12 HP safety valves (each circuit) High pressure safety valve connection inch 3/4” G Low pressure switch barg (1) --- With nominal air flow; mixture outlet temperature 10° C; full load; R410A refrigerant. 3 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 13: Technical Data

    (2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 14 (2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 15 (2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 16 (2) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (3) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 4 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 17 (3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 5 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 18 (3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 6 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 19 (3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 7 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 20 (3) --- Measured with outdoor temperature 35 C; 1m from the unit; free field conditions; according to ISO 3744. ° (4) --- With outdoor temperature 35 C; calculated according to ISO 3744. ° 4 -- 8 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 21: Mechanical Specifications

    The units are designed for being used with refrigerant R410A. Compressor The Liebert HPC ---S 006 ---022 series is equipped with two hermetic, scroll compressors specifically de- signed for application in refrigeration systems. Tandem compressors consist of two compressors which can be equal or different size models; they offer advantages over single compressors with equivalent capacity such as: Efficient capacity control - through cycling one or two compressors.
  • Page 22 Evaporators Liebert HPC ---S 006 ---022 units are equipped with direct expansion, weld ---brazed plate type evaporat- ors, designed, constructed, tested (pressure test on both refrigerant and water sides) and documented to comply with PED 97/23/EC standards. The corrugation (typical angle) and the design of each plate have been thoroughly analyzed and thus optimized to better meet the physical features of the refrigerant (R410A) and provide for an optimal refrigerant distribution.
  • Page 23 Freecooling Execution Liebert HPC ---S 006 ---022 models in the ”Freecooling execution” are designed with an integrated free- cooling system consisting of: cooling coils with copper tubes and aluminium fins, mounted in vertical configuration;...
  • Page 24 Recirculating Pumps (Option) All the models of the Liebert HPC ---S 006 ---022 series can be equipped with one or two water circulating pumps, factory ---piped.
  • Page 25 The company is not responsible for damage due to incorrect or improper use of the product and it reserves the right to change technical specifications without any prior notice. 5 -- 5 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 26 The machine is supplied with a final test certificate and a declaration of conformity with the norms. All Liebert HPC ---S 006 ---022 units are ” ” marked. Accessories...
  • Page 27 CEA 210/5 FHE 40--- 160/40 FHE 40--- 200/55 210/4 370/5 40--- 160/30 Nominal Motor Power 1.50 1.85 3.00 4.00 5.50 Noise Level dB(A) (*) --- According to ISO 3744 5 -- 7 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 28: Other Accessories

    300 litres Other Accessories The following accessories can be installed as an option: Anti ---vibrating mounts (spring / rubber). Dee shackle UNI 1947. Coldfire IP40 remote box. Water filter. 5 -- 8 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 29: Controls

    Input for Remote on ---off and Volt---free contacts for simple remote monitoring of alarms and warn- ings are available. Up to 16 Liebert HPC ---S 006 ---022 units can be easily linked together on a network to provide teamwork mode, stand ---by operation and duty cycling without additional hardware. Reliability is not affected if there are problems on the data communication buses, because the units return auto- matically to the stand ---alone mode.
  • Page 30 The IS cards and other gateway represent the communication managers portfolio which allow the integ- ration of the Liebert HPC ---S 006 ---022 units into the most diffused Building Management Systems. The most diffused are: SNMP , HTTP , MODBUS and LONWORK.
  • Page 31: Performance Adjustment Factors

    1800 0,988 1,015 Unit performance reported in the tables are given for sea level conditions. For different altitude, performances should be corrected with the correction factors shown above. 7 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 32: Sound Levels

    94.0 CB0014 FB0014 94.5 CB0015 FB0015 94.5 CB0018 FB0018 96.0 CB0019 FB0019 96.5 CB0022 FB0022 97.0 Note: Sound power levels tolerance for each octave band: --- 0/+2 dB 8 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 33 97.5 CG0009 FG0009 97.5 CG0011 FG0011 97.5 CG0014 FG0014 99.0 CG0015 FG0015 99.0 CG0018 FG0018 99.0 Note: Sound power levels tolerance for each octave band: --- 0/+2 dB 8 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 34 Sound power levels tolerance for each octave band: --- 0/+2 dB In the ”G” version chiller, the characteristics of the ”EC” fans can achieve significant noise reductions according to their speed (RPM). 8 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 35: Electrical Data

    High head pressure pump --- Nominal power 1,85 High head pressure pump --- Max. current (1) --- Outdoor temperature 35° C; water inlet/outlet temperature 12/7° C; R410A refrigerant. 9 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 36: Cea 210/3

    1,85 High head pressure pump --- Max. current (1) --- Outdoor temperature 35° C; fluid inlet/outlet temperature 15/10° C; 70 --- 30% water --- glycol mixture; R410A refrigerant. 9 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 37: Application Considerations

    014 --- 015 --- 018 Tab. 10b --- Weight distribution without tank and pumps Weight distribution (kg) Total Models Size (kg) 1060 1177 1196 1426 1436 1480 1072 1388 1408 1452 10 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 38 1513 1633 1652 2072 2082 2126 1366 1410 1528 2034 2052 2096 1166 1183 1624 1829 1950 1971 2480 2496 2536 1166 1615 1726 1845 2444 2464 2504 10 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 39 CB0 / FB0 018 --- 019 --- 022 3 Ventilators 485622 CG0 / FG0 014 --- 015 --- 018 Each kit is complete with stainless steel fixing screws and plain washers for unit assembly. 10 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 40 CB0 / FB0 009 --- 011 --- 014 --- 015 ≈8 CG0 / FG0 007 --- 009 --- 011 ≈4 CB0 / FB0 018 --- 019 --- 022 CG0 / FG0 014 --- 015 --- 018 10 -- 4 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 41 4000 1640 1678 4000 1630 1690 4000 1623 1728 2000 3000 1343 1055 3000 1372 1147 3000 1293 1266 4000 1653 1643 4000 1638 1661 4000 1626 1702 10 -- 5 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 42 4000 1924 2013 4000 1915 2025 4000 1903 2063 2000 3000 1537 1300 3000 1548 1392 3000 1467 1511 4000 1940 1978 4000 1926 1996 4000 1910 2037 10 -- 6 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 43 Minimum distance between 2 units from condensing coil side = 2 m. Do not obstruct the air exiting the fans for a minimum distance of 2.5 m. (*) Extraordinary maintenence area for unit with tank: 1000 mm. 10 -- 7 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 44: Dimensional Data

    Dimensional Data 11 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 45 Dimensional Data 11 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 46 Dimensional Data 11 -- 3 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 47: Refrigerant Circuit

    Low pressure switch Mechanical expansion valve Electronic expansion valve Evaporator EEV temperature sensor Transducer pressure sensor (High pressure control) Safety valve External air temperature sensor Condenser Condenser fans 12 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 48: Hydraulic Circuit

    Hydraulic Circuit 13 -- 1 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 49 Hydraulic Circuit 13 -- 2 Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012...
  • Page 51 De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is: Vaimistaja vakuuttaa täten, että tämä tuote täyättää seuraavien EU--- direktiivien vaatimukset: Since the Liebert HIROSS Company has a policy of continuous product improvement, it reserves the right to change design and Produsent erklærer herved at dette produktet er i samsvar med EU--- direktiver:...
  • Page 52 2008 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. Emerson Network Power...