Model Number Description

Model Nomenclature / Digit Numbers
Model Number Description
1 2 3 4 5 6
C
G 0 0 1
Specification
C
= Air cooled
Chiller
F
= Freecooling
Chiller
Liebert HPC---S 006---022
Digits 1, 2, 3, 4, 5, 6 --- Base unit
Base unit main features
R410A refrigerant;
D
One refrigeration circuit;
D
HP and LP gauges;
D
Fans speed control (TRIAC or EC according B or G
D
version); on B versions, different options with EC fans
are available;
On digit 11 base version B, opt. B & D + G version
D
opt. C compressors jacket if necessary;
On digit 11 G version opt. D compressors jacket +
D
compressor's box insulated if necessary;
Expansion valve:
TXV (Thermostatic expansion
D
EEV (Electronic Expansion Valve)
Flow switch and Hydraulic Kit (Hydraulic Kit =
D
expansion vessel and safety valve);
Evaporator electric heater + tank electric heater will
D
protect piping too (only if pump/s are fitted on unit);
Electrical panel ventilation;
D
Buffer tank of 100, 200 and 300 litres (1, 2 and 3 fans).
D
Digit 7 --- Display and Switch
A = FTE display
B = FTE display + Network Switch
E = iCOM Coldfire display large
F = iCOM Coldfire display large + Network Switch
Digit 8 --- Soft starter
0 = None
1 = With compressors soft starter
Digit 9 --- Monitoring
0 = None
1 = IS Housing (no IS Card included)
2 = Web card
3 = Modbus card
4 = Sitescan card
5 = Web card + Modbus card
6 = Web card + Sitescan card
7 = Modbus card + Sitescan card
8 = Bacnet card (Bacnet or Modbus over IP)
Liebert HPC --- S 006--- 022--- PD--- 273571--- 01.03.2012
Valve) on B version;
on G version;
7
8
9 10 11 12 13 14 15 16 17 18
1
Cooling Capacity
Cooling capacity (x 10 = kW)
Refrigerant
0
= R410A
Versions
B
= Base version
G
= High efficiency class version
Digit 10 --- Buffer tank
0 = None
1 = With buffer tank
2 = With buffer tank + electric heaters (only for chiller
models)
Digit 11 --- Fans options
A = TRIAC control and 900 mm fans
B = TRIAC control and 800 mm fans
C =EC---Fans, 900 mm
D =EC---Fans, 800 mm
Digit 12 --- Pumps group (expansion tank and water
safety valve always included as standard)
1 = No pumps
2 = With 1 pump LP (low pressure)
3 = With 1 pump HP (high pressure)
4 = With 2 pumps LP (low pressure)
5 = With 2 pumps HP (high pressure)
Digit 13 --- Free
Digit 14 --- Electric panel options
0 = None
1 = With electric heaters
A = Fast start ramp
B = Fast start ramp and electric heaters
Digit 15 --- Evaporator antifreeze protection
0 = None
1 = With evaporator antifreeze protection
2 = With evaporator and pipe antifreeze protection
Digit 16 --- Compressor power factor correction
0 = None
1 = With compressors power factor capacitors
Digit 17 --- Coil metal filter / Protection grid
0 = None
1 = With coil metal filter
Digit 18 --- Special requests
0 = None
X = As specified