Lower Front Filler Panel; Gas Line Installation; Gas Pressure Requirements; Gas Supply Line Sizing - Lennox FIRESTAR MERIT GC3 Installation And Operation Manual

Merit series b-vent fireplace
Table of Contents

Advertisement

Lower Front 2" Filler Panel
The FireStar™ insert comes with a 2" panel to fill the space between the
insert bottom and the hearth extension. If the hearth elevations necessitate,
the insert may be installed directly on the hearth without the leveling bolts
or filler panel. To install the panel, insert the four tabs on the top of the
panel into the corresponding slots in the insert bottom. Open the insert
side doors, remove the two socket head screws from the hardware bag
and install them (using a 5/32" hex wrench) through the insert bottom
into the filler panel. A tall adjustable filler panel is also available.

Gas Line Installation

After leveling, position the insert in the fireplace, holding it about six
inches out from its final location.
CAUTION: Specific Hearth Requirements apply (see Clearances
and Specifications).
The Firestar gas insert must be connected to the gas line in
accordance with local codes and / or the National Fuel Gas
Code, Z223.1-latest edition, also known as NFPA 54 (In Canada,
the current CAN/CSA B149.1 installation code). Included in the
manual package is an 8" gas nipple. Locate the threaded gas
inlet on the lower left of the insert. Thread the 8" gas nipple
into the inlet with a teflon sealer or equivalent. Attach the gas
supply line to this hard pipe. The hard pipe can receive a 3/8"
inch female iron pipe coupling, or a shut off valve. After con-
necting the gas line, all joints in the line and connections at
the valve should be checked for leaks before final positioning
of the unit. Conduct a gas leakage test of the appliance piping
and control system downstream of the shutoff valve in the supply
line to the appliance.

Gas Pressure Requirements

A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS
APPLIANCES I !
The most important item to check during the initial installation
and the first thing to check when operating problems occur is
gas pressure! This appliance will not function properly unless
the required gas pressure is supplied. See Table 1 for gas
pressure requirements.
Two pressure taps are provided on the insert's valve to check gas pressures.
The taps are located below the on/off/pilot knob (see Figure 14). The left
tap is the inlet (supply) pressure side. To check inlet pressure (with the
insert burning), insert a small phillips screwdriver into the tap and turn a
half turn counter-clockwise. Cover the tap with the line from a manometer
and check the pressure. Close
tap gently but securely after
completing the check. The
manifold (outlet) tap is to the
right of the inlet tap.
12
Gas Line Installation
After leveling, position the insert in the fireplace --- holding it
about six inches out from its final location.
Caution: Specific Hearth Requirements apply (see Clearances
and Specifications). The
gas line in accordance with local codes and / or the National Fuel
Gas Code---
(In Canada, the current CAN/CSA B149.1 installation code)
Included in the manual package is a 8" gas nipple. Locate the
threaded gas inlet on the lower left of the insert. Thread the
8" gas nipple into the inlet with a teflon sealer or equiv. Attach
the gas supply line to this hard pipe. The hard pipe can receive
a 3/8" inch female iron pipe coupling, or a shut off valve. After
connecting the gas line, all joints in the line and connections
at the valve should be checked for leaks.
Inlet Elbow
Inlet
Off/On/Pilot
Pressure
Manifold
Tap
Pressure Tap
Flame Height
Outlet
Adjustment
Orifice
Figure 14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
To check manifold pressure (with the insert burning at the high burn
setting) insert a small phillips screwdriver into the tap and turn a half
turn counter-clockwise. Cover the tap with the line from the manometer
and check the pressure. Again close the tap gently but securely after
completing the check. Check the taps for gas leaks with a gas leak test
solution (retighten if necessary).
If the pressure is not sufficient, make sure the gas supply line is large
enough, the supply regulator is properly adjusted and the total gas load
for the residence does not exceed the amount supplied.
Propane tanks are at pressures that will cause damage to valve com-
ponents. Verify that the tanks have step down regulators to reduce the
pressure to safe levels.
These appliances must be isolated from the gas supply piping system
(by closing their individual manual shut-off valve) during any pressure
testing of the gas supply piping system at test pressures equal to or
less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be discon-
nected from the gas supply piping system during any pressure testing
of that system at pressures greater than 1/2 psig (3.5 kPa).
Fuel
Inlet Pressure
Designer™
must be connected to the
Type
Desired
Minimum
Z223.1-latest edition, also known as NFPA 54
Natural
7" WC
5" WC
Gas
LP Gas
11" WC
10.5" WC
Table 1

Gas Supply Line Sizing

The proper gas line diameter must be selected to run from the supply regu-
lator to the insert. Refer to the Table 2 for proper gas pipe diameters.
Note: Some areas allow copper tubing - check with local approval agen-
cies and codes.
COPPER TUBING NOT ALLOWED IN MASSACHUSETTS IN
NATURAL GAS INSTALLATIONS, NEVER USE GALVANIZED OR
PLASTIC PIPES.
Pipe Length
Schedule 40 Pipe
(Feet from Supply
Inside Diameter
Regulator)
(Black Pipe)
Natural Gas
/
1
"
2
0-10
(1.3 cm)
/
1
"
2
10-40
(1.3 cm)
/
1
"
2
40-100
(1.3 cm)
/
3
"
4
100-150
(2.0 cm)
/
3
"
4
150-200
(2.0 cm)
Table 2
G
s
l
s
as
upply
ine
izinG
The proper gas line diameter must be selected to
supply regulator to the stove. Refer to the follo
proper gas pipe diameters.
Manifold Pressure
NOTE: Some areas allow copper tubing - check with
Maximum
On Hi
On Lo
agencies and codes.
Fire
Fire
COPPER TUBING NOT ALLOWED IN MASSAC
.
10.5" WC
3.5" WC
1.7" WC
NATURAL GAS INSTALLATIONS, NEVER USE GA
PLASTIC PIPES.
13" WC
10.0" WC
5.4" WC
Tubing, Type L Outside Diam-
eter (Copper)
(Do Not Use Copper in Massachusetts
with Natural Gas)
L.P.
Natural Gas
L.P.
/
/
/
3
1
3
"
"
8
2
8
(1.0 cm)
(1.3 cm)
(1.0 cm)
/
/
/
1
"
5
1
"
2
8
2
(1.3 cm)
(1.6 cm)
(1.3 cm)
/
/
/
1
3
1
"
"
2
4
2
(1.3 cm)
(2.0 cm)
(1.3 cm)
/
/
/
1
7
3
"
"
2
8
4
(1.3 cm)
(2.3 cm)
(2.0 cm)
/
/
/
1
7
3
"
"
2
8
4
(1.3 cm)
(2.3 cm)
(2.0 cm)
"
"
"
"
"

Hide quick links: