Device Overload Monitoring (Ixt) - Lenze 8400 Reference Manual

Inverter drives
Hide thumbs Also See for 8400:
Table of Contents

Advertisement

5
Motor control (MCTRL)
5.14
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.14.1

Device overload monitoring (Ixt)

C00064/1...3
Parameter
C00064/1
C00064/2
C00064/3
Highlighted in grey = display parameter
• If the device utilisation reaches the warning threshold set in
• The error response set in
• The
"OC5: Ixt
• A setting of
• If the device utilisation reaches the permanent shutdown limit 110 %:
• The error response "Fault" will be carried out.
• The
"OC9: Ixt overload shutdown
172
displays the device utilisation (ixt) in [%] in different time intervals:
Info
Device utilisation (Ixt)
• Maximum value of pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
Device utilisation (Ixt) 15s
• Pulse utilisation over the last 15 seconds (only for loads >160 %).
Device utilisation (Ixt) 3 min
• Permanent utilisation over the last 3 minutes.
C00604
overload" error message will be entered into the Logbook.
C00604
= "0: No Reaction" deactivates the monitoring.
C00123
will be carried out (Lenze setting: "Warning").
limit" error message will be entered into the logbook.
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
(Lenze setting: 100 %):