Annual Maintenance - Ariston Clas 24 FF Installation And Servicing Instructions

Ariston wall hung gas boilers type c
Hide thumbs Also See for Clas 24 FF:
Table of Contents

Advertisement

maintenance guide

Annual Maintenance

5. ANNUAL MAINTENANCE
Plate heat exchanger
Maintenance Interval: As necessary
How: To measure specification of DHW performance.
By-pass & Safety valve
Maintenance Interval: Annually
How: Visual inspection / Clean as necessary
Central heating filter
Maintenance Interval: Annually
How: Visual inspection / Clean as necessary
Flow switch operation
Maintenance Interval: Annually
How: Visual inspection / Clean as necessary
/ Check flow rate
Expansion vessel
Maintenance Interval: Annually
How: Check air pressure is at 1 bar (System drained)
Ignition & detection electrodes
Maintenance Interval: Annually
How: Visual inspection / Clean as necessary / Distance from the
burner / Ionisation current more than 1 —A
Burner
Maintenance Interval: Annually
How: Visual inspection / Clean as necessary
Fan
Maintenance Interval: Annually
How : Visual inspection / Clean as necessary
Primary Heat exchanger
Maintenance Interval: Annually
How : Visual inspection / Clean as necessary
Pump
Maintenance Interval: At the first ignition and annually
How: Check that the AAV is open /
Visual inspection / Clean as necessary
62