Description
4
2
3
Parallel curve shift Zone 1 Off set
To adapt the heating curve to the system requirements, shift the curve in parallel so that the calculated fl ow temperature
is modifi ed, in addition to the room temperature.
By accessing this parameter and turning knob "5" (Figs 1 and 2 - page 4), the curve can be shifted in a parallel manner.
The value is indicated on the display, from -20 to +20.
4
2
4
Room sensor Infl uence to calculate the
set-point temperature - Thermoregulation
enabled-
4
2
5
Maximum Central Heating Temperature Zone1
4
2
6
Minimum Central Heating Temperature Zone 1
4
3
DIAGNOSTICS
4
3
0
Room Temperature Zone 1 - only active when the BUS device is connected
4
3
1
Flow Temperature Zone 1 - only active when the BUS device is connected
4
3
2
Zone 1 Heat Request
4
3
3
Zone 1 Pump status
4
4
ZONE 1 DEVICES
4
4
0
Zone 1 Pump control
5
ZONE 2 PARAMETER
5
0
ZONE 2 SET TEMPERATURE
5
0
0
Set Day Temperature Zona 2
5
0
1
Set Night Temperature Zona 2
5
0
2
Fix temperature central heating
5
1
Service code
5
2
SET ZONE 2
5
2
0
Zone 2 Temperature range
DO NOT MODIFY
5
2
1
Select Type of Thermoregulation
5
2
2
Zone 1 Slope
When an outdoor sensor is used, the boiler calculates the most suitable delivery
temperature, taking into account the outside temperature and type of system.
The type of curve should be selected in correspondence with the projected
temperature of the system and the nature of the dispersions present in the
structure. For high-temperature systems, one of the curves depicted in the chart
may be chosen.
1.0 - 1.5 = Standard System
2.0 - 3.5 = Convector Radiators
Note: The Outdoor Sensor should only be used when the boiler is used for central heating only.
settings - adjustment - problem identifi cation menus
range
from - 20 to + 20
from 0 to 20
If set to = 0 the room temperature doesn't infl uence the calculation of the set-point.
If set to = 20, the room temperature has the maximun infl uence to calculate the set-
point - only active when the BUS device is connected
from 40 to 82 (°C)
from 40 to 82 (°C)
0 = OFF 1 =ON
0 = OFF 1 =ON
0 = OFF 1 =ON
from 16 to 30 (°C)
from 16 to 30 (°C)
from 35 to85 (°C)
0= Low Temperature
1= High Temperature
0 = Fixed Flow Temperature
1 = Basic Thermoregulation
2 = Room Temperature only
3 = Outdoor Temperature only
4 = Room + Outdoor
Temperature
from 0_2 to 3_5
0
20
82
40
Active only with MGZ/MCM Kit
Active only with MGZ/MCM Kit
19
only active when the BUS device is
connected
16
70
To set only with Fixed Flow Temperaure of
Thermoregulation (see 521)
222
Press +/- to select code 234 and press
M
/O
ENU
K
ONLY FOR SERVICE
Active only with MGZ/MCM Kit
1
To enabled thermoregulation press Auto
button. The display show the symbol.
1_5
Only enabled when an outdoor sen-
sor is installed
see graph previous page
prameter 4 2 2