300 min.
400 min.
Flue Header  Equivalent lengths (m) ‐ flue pipe 
Flue Header 
Load kW 
Size mm 
350 
250 
400 
250 
600 
250 
800 ‐ Max 
250 
Flue Header 
Flue  
Load kW 
Size mm 
350 
300 
400 
300 
600 
300 
800 
300 
1000 
300 
1200 ‐ Max 
300 
Table C5.1 - Cascade Flue equivalent lengths - refer to fig. C5.1
Concentric Flue - Cuttable extension pieces
When cutting a concentric flue extension piece,
care must be taken to ensure that the inner section
is always cut 10mm longer than the outer section to
allow sections to be joined correctly.
Do not cut all the way through both sections at the
same length. Cut the outer section first and then
the inner section 10mm longer.
HAMWORTHY HEATING LTD
225
750 crs
140
Max L 
45° 
100 
100 
75 
50 
Equivalent lengths (m) ‐ flue pipe 
Max L 
45° 
100 
100 
100 
90 
50 
30 
175‐350kW (130/250mm) 
90° 
Cascade flue kit  
 
6.5 
Extension kit 
6.5 
6.5 
Options: 
6.5 
130Ø * 1m straight ‐ st/steel 
250Ø * 1m straight ‐ st/steel 
250Ø 87° Elbow ‐ st/steel 
90° 
250Ø 45° Elbow ‐ st/steel 
250/300Ø Expander ‐ st/steel 
300Ø * 1m straight ‐ st/steel 
300Ø 87° Elbow ‐ st/steel 
300Ø 45° Elbow ‐ st/steel 
57
FLEET H series
Figure C5.1 - Cascade
flue system 250mm Ø
HHL Part no 
562511095 
562511097 
 
532511220 
532511213 
532511208 
532511203 
532511224 
532511216 
532511209 
532511204 
500001216/D