Performance Table - McQuay MCK020A Technical Manual

Ceiling cassette split systems
Hide thumbs Also See for MCK020A:
Table of Contents

Advertisement

P P P P P erf
erf
erf
or
or
mance
mance
mance T T T T a a a a b b b b le le le le
erfor
erformance Table
ormance
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC
at those temperatures which are not stated out in the table.
Example:
Model: MCK 0 20A / MLC 0 20B
Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Solution:
Overall
Based on the Performance table on Pg.(39),
1. Refer to the Indoor DB column,
-
23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
-
15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C WB
and 17°C WB during 24°C indoor DB is required)
3. Refer to the Outdoor DB column,
37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
-
Please follow the steps below in order to get the required capacity.
st
1
Step
Extrapolation of Indoor WB
Find TC, SC for
15°C WB
(a) Indoor: 24°C DB,
Outdoor: 35°C DB
15°C WB
(b) Indoor: 24°C DB,
Outdoor: 40°C DB
nd
2
Step
Interpolation of Indoor DB
Find TC, SC for
23°C DB
(a) Indoor:
, 15°C WB
Outdoor: 35°C DB
23°C DB
(b) Indoor:
, 15°C WB
Outdoor: 40°C DB
35
rd
3
Step
Interpolation of Outdoor DB
Find TC, SC for
(a) Indoor: 23°C DB, 15°C WB
37°C DB
Outdoor: