Primary and second rack clearance notes and floor loading
The following explanatory notes apply to the preceding floor clearance drawings for the
primary and second rack.
*1: Clearance (a+b) depends on the floor load rating and clearance "c". Required
clearances for various floor load ratings are shown below.
*2: Clearance between racks must be at least 10 mm. If the kickplate is installed after
rack placement, allow 100 mm.
Floorload
rating
(kg/mm2)
500
450
400
350
300
Additional primary and second rack floor loading and clearance notes:
•
Decide actual clearances in consultation with the construction specialist
responsible for installation. They may vary depending on the size and layout of
the system and building conditions.
•
When multiple disk arrays are arranged in a row, base your clearance values on
the requirements of the largest disk array.
•
Generally, clearances ("c") should be as large as allowable.
Required clearance (a + b) mm
c = 0
c = 200
100
0.00
300
200
600
400
1000
800
1600
1300
HP StorageWorks XP10000 Disk Array Site Prep Guide
Clearance (c) mm
c = 400
c = 600
0.00
0.00
300
600
1100
c = 1000
0.00
0.00
0.00
0.00
200
0.00
500
200
900
600
39