6.6 Output override

This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.
The output override is used to disable one or more of the controlled
components. This could among others be useful in a service
situation.
Action:
Purpose:
Choose 'MENU' in any of the overview
displays
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Choose common controller settings
Confirm
Choose 'Output override'
Confirm
Choose a controlled component
Confirm
Adjust the status of the controlled
component:
Motorized control valve: AUTO, STOP,
CLOSE, OPEN
Pump: AUTO, OFF, ON
Confirm status change
Remember to change the status back again as soon as an override
is not required any longer.
A314.1 and A314.2 only:
The unit M2 is controlled by a 0–10 volt (0–100%) signal. It can be
set to AUTO or ON.
AUTO:
Normal control (0–100%)
ON:
The 0–10 volt signal is set as a percentage.
A314.3 only:
The output V1 is controlled by a 0–10 volt (0–100%) signal. It can
be set to AUTO or ON.
AUTO:
Normal control (0–100%)
ON:
The 0–10 volt signal is set as a percentage.
Danfoss District Energy
ECL Comfort 210 / 310, application A214 / A314
Examples:
M1, P1 etc.
Controlled components
When the selected controlled component (output) is not 'AUTO' , the
ECL Comfort controller does not control the component in question
(pump or motorized control valve e.g.). Frost protection is not active.