Danfoss ECL Comfort 210 Installation Manual page 30

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
A314.2 example c
Ventilation system with heating, passive cooling (outside air) and constant room temperature control. Analog controlled speed of rotary
heat exchanger (M2) for heat recovery.
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
30
DEN-SMT/DK
ECL Comfort 210 / 310, application A214 / A314
S
1
P 2
A
ECL 310 + ECA 32
R6
M1
S 5
X3
F1
S 6
S 7
VI.GU.A1.02
S 4
ID no.: Recommended
setting:
11676
5 °C
11656
5 °C
11616
0
11616
1
11636
0
11636
1
Danfoss District Energy