Icc Control Operation - Rheem ASL-JEC 18 Seer Installation Instructions Manual

Air-cooled condencing units
Table of Contents

Advertisement

Lower case "c" indicates first stage cooling operation
2) Second Stage Cooling Operation – When the ICC receives a command for second stage
cooling operation, an upper case "C" is displayed on the 7-segment LEDs.
Lower case "c" indicates first stage cooling operation
2) Second Stage Cooling Operation – When the ICC receives a command for second stage
cooling operation, an upper case "C" is displayed on the 7-segment LEDs.
Upper case "C" indicates second stage cooling operation
3) First Stage Heating Operation - When the ICC receives a command for first stage
heating operation, "h1" is displayed on the 7-segment LEDs.
Upper case "C" indicates second stage cooling operation
3) First Stage Heating Operation - When the ICC receives a command for first stage
heating operation, "h1" is displayed on the 7-segment LEDs.
"h1" indicates first stage heating operation
13.X Serial Communication ICC Control Operation
12.4 Comfort Control
I I n n s s t t a a l l l l a a t t i i o o n n V V e e r r i i f f i i c c a a t t i i o o n n
Installation Verification
• 24V AC power on R&C must be present at the ICC for it to operate
24V AC power on R&C must be present at the ICC for it to operate
• Line voltage must be present at the ICC for the compressor and the outdoor fan
Line voltage must be present at the ICC for the compressor and the outdoor fan to operate
to operate
The ICC displays a "0" for standby mode. Standby mode indicates line voltage and 24VA
• The ICC displays a "0" for standby mode. Standby mode indicates line voltage
and 24VAC are present at the ICC and there is not a command for unit operation
are present at the ICC and there is not a command for unit operation from the serial
from the serial communicating thermostat.
communicating thermostat.
C C o o m m m m a a n n d d f f o o r r C C o o m m p p r r e e s s s s o o r r O O p p e e r r a a t t i i o o n n ( ( Y Y 1 1 L L E E D D ) )
• If a command for compressor operation is received by the ICC (first stage/second
Command for Compressor Operation (Y1 LED)
stage cooling or first stage/second stage heating), the red Y1 LED will illuminate.
If a command for compressor operation is received by the ICC (first stage/second stage
• The ICC has an on/off fan delay of one (1) second for each stage of heating or
The ICC has a built in 3-minute time delay between compressor operations to protect the
cooling or first stage/second stage heating), the red Y1 LED will illuminate.
cooling.
The ICC has a built in 3-minute time delay between compressor operations to protect the
compressor against short cycling. The 7-segment LEDs will flash "c", "C", "h1", or "h2
The ICC has an on/off fan delay of one (1) second for each stage of heating or cooling.
• The ICC ignores the low pressure control for the first 90 seconds of compressor
compressor against short cycling. The 7-segment LEDs will flash "c", "C", "h1", or "h2
operation.
while the short cycle timer is active and a command for unit operation is received.
The ICC ignores the lower pressure control for the first 90 seconds of compressor operatio
while the short cycle timer is active and a command for unit operation is received.
• The dual 7-segment LED displays five (5) operational status codes.
On heat pumps, the ICC ignores the LPC during the defrost cycle.
1 1 ) ) F F i i r r s s t t S S t t a a g g e e C C o o o o l l i i n n g g O O p p e e r r a a t t i i o o n n – When the ICC receives a command for first
The 7-segment LED can display five (5) codes during a command for unit operation:
stage cooling operation, a lower case "c" is displayed on the dual 7-segment LEDs.
1) First Stage Cooling Operation – When the ICC receives a command for first stage
cooling operation, a lower case "c" is displayed on the 7-segment LEDs.
2 2 ) ) S S e e c c o o n n d d S S t t a a g g e e C C o o o o l l i i n n g g O O p p e e r r a a t t i i o o n n – When the ICC receives a command for
second stage cooling operation, an upper case "C" is displayed on the dual 7-
segment LEDs.
3 3 - - m m i i n n u u t t e e A A n n t t i i - - s s h h o o r r t t C C y y c c l l e e T T i i m m e e r r
• The ICC has a built in 3-minute time delay between compressor operations to
protect the compressor against short cycling. The dual 7-segment LEDs will flash
"c" or "C" while the short cycle timer is active and a command for unit operation is
received.
• The 3-minute time delay can be bypassed when a command for compressor
operation is present by pressing the TEST button for 1 second and releasing. The
compressor will begin operation and the dual 7-segment will stop flashing.
The 3-minute time delay can be bypassed when a command for compressor operation is
The 3-minute time delay can be bypassed when a command for compressor operation is
present by pressing the TEST button for 1 second and releasing. The compressor will begi
present by pressing the TEST button for 1 second and releasing. The compressor will begi
operation and the 7-segment will stop flashing.
operation and the 7-segment will stop flashing.
30 Second Minimum Run Timer
30 Second Minimum Run Timer
The ICC has a built in 30 second minimum unit run time. If a command for compressor
The ICC has a built in 30 second minimum unit run time. If a command for compressor
operation is received by the ICC and the command is removed, the compressor will continu
operation is received by the ICC and the command is removed, the compressor will continu
to operate for 30 seconds. The 7-segment LEDs will flash "c", "C", "h1", or "h2 while the
to operate for 30 seconds. The 7-segment LEDs will flash "c", "C", "h1", or "h2 while the
minimum run timer is active.
2

ICC Control Operation

Zero (0) displayed
The unit is in standby
Zero (0) displayed
The unit is in standby
Flashing lower case c
Flashing lower case c
A command for first stage cooling has been received
A command for first stage cooling has been received
Lower case "c" indicates first stage cooling operation
Flashing upper case C
Flashing upper case C
A command for second stage cooling has be received
A command for second stage cooling has be received
Upper case "C" indicates second stage cooling operation
Flashing lower case h and 1
Flashing lower case h and 1
A command for first stage heating has been received
A command for first stage heating has been received
Flashing lower case c
A command for first stage cooling has been received
Flashing lower case h and 2
Flashing upper case C
Flashing lower case h and 2
A command for second stage cooling has been received
A command for second stage heating has been received
A command for second stage heating has been received
21