3.3 Operational Issues

IMPORTANT: Locate the unit in a manner that will not prevent, impair or com-
promise the performance of other equipment horizontally installed in proximity
to the unit. Maintain all required minimum distances to gas and electric meters,
dryer vents, exhaust and inlet openings. In the absence of National Codes, or
manufacturers' recommendations, local code recommendations and require-
ments will take precedence.
Refrigerant piping and wiring should be properly sized and kept as short as
possible to avoid capacity losses and increased operating costs.
Locate the unit where water run off will not create a problem with the equip-
ment. Position the unit away from the drip edge of the roof whenever possible.
Units are weatherized, but can be affected by the following:
o Water pouring into the unit from the junction of rooflines, without protective
guttering. Large volumes of water entering the heat pump while in operation
can impact fan blade or motor life, and coil damage may occur to a heat
pump if moisture cannot drain from the unit under freezing conditions.
o Freezing moisture, or sleeting conditions, can cause the cabinet to ice-over
prematurely and prevent heat pump operation, requiring backup heat, which
generally results in less economical operation.
Closely follow clearance recommendations on Page 6.
o 24" to the service panel access
o 60" above heat pump fan discharge (unit top) to prevent recirculation
o 6" to heat pump coil grille air inlets
3.4 For Units With Space Limitations

FOR CONDENSERS WITH SPACE LIMITATIONS

In the event that a space limitation exists, we will permit the following clearances:
Single Unit Applications: Clearances below 6 inches will reduce unit capacity and
efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clearances.
Multiple Unit Applications: When multiple condenser grille sides are aligned, a 6-
inch per unit clearance is recommended, for a total of 12" between two units. Two
combined clearances below 12 inches will reduce capacity and efficiency. Do not
reduce the 60-inch discharge, or 24-inch service, clearances.

3.5 Customer Satisfaction Issues

The condensing unit should be located away from the living, sleeping and
recreational spaces of the owner and those spaces on adjoining property.
To prevent noise transmission, the mounting pad for the outdoor unit should not
be connected to the structure, and should be located sufficient distance above
grade to prevent ground water from entering the unit.

3.6 Unit Mounting

If elevating the condensing unit, either on a flat roof or on a slab, observe the
following guidelines.
The base pan provided elevates the heat pump 3/4" above the base pad.
If elevating a unit on a flat roof, use 4" x 4" (or equivalent) stringers positioned
to distribute unit weight evenly and prevent noise and vibration (see Figure 2).
NOTE: Do not block drain openings shown in Figure 1.
3.7 Factory-Preferred Tie-Down Method for Outdoor Units
IMPORTANT: The Manufacturer approved/recommended method is a guide to secur-
ing equipment for wind and seismic loads. Other methods might provide the same
result, but the Manufacturer method is the only one endorsed by Manufacturer for
securing equipment where wind or earthquake damage can occur. Additional informa-
tion is available in the PTS (Product Technical Support) section of the Manufacturer
website Rheemote.net and can be found as a listing under each outdoor model. If you
do not have access to this site, your Distributor can offer assistance.