[ II Restrictions ]
2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected
(manual address setup for both indoor and outdoor units)
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) When the number of the connected indoor units is as
shown in the table below, one or more transmission
boosters (sold separately) are required.
To connect two transmission boosters, connect them in
parallel. (Observe the maximum number of connectable
indoor units that are listed in the specifications for each
outdoor unit.)
When the 200 and 250 models are not in-
cluded in the connected indoor units
When the 200 and 250 models are includ-
ed in the connected indoor units
HWE10020
L1
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OC
BC
51
53
TB02
TB3
TB7
M1 M2
M1 M2
S
M1 M2
S
M1 M2
S
TB02
57
BS
* If the BC address overlaps any of the addresses that are assigned to either the OC or BS, use a different, unused address.
OC, and BS addresses (lowest indoor unit address in the group plus +50) have higher priority than the BS address.
Number of transmission
booster (sold separately)
required
1 unit
2 units
27 - 50
units
21 - 39
40 - 50
units
units
L2
L3
Group
IC
01
TB5
TB15
M1M2
S
1 2
A1 B2
MA
L12
Group
IC
03
TB5
TB15
M1M2
S
1 2
A1 B2
MA
IC
07
TB5
TB15
M1M2
S
1 2
A1 B2
MA
The table above shows the number of transmission
boosters that is required by the system with three BC
controllers. For each BC controller that is subtracted
from the above-mentioned system, two additional indoor
units can be connected.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 1.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as [5] 1.
-
- 32 -
Interlock operation with the ventilation unit
L4
Group
LC
IC
02
05
TB5
TB15
TB5
M1M2
M1M2
S
1 2
S
A1 B2
MA
L13
LC
IC
04
06
TB5
TB15
TB5
M1M2
M1M2
S
1 2
S
IC
08
TB5
TB15
M1M2
S
1 2
A1 B2
MA
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp250Pury-rp300yjm-a

Table of Contents