[ VI Refrigerant Circuit ]
(3) GB type
Symbols
Part name
(functions)
Thermistor
TH12
(Bypass
outlet tem-
perature)
TH15
(Bypass in-
let tempera-
ture)
Solenoid
SV A
valve
SV B
SV C
LEV
LEV3
HWE10020
Part
Usage
code
LEV control (Superheat)
LEV control (Superheat)
Provides refrigerant to indoor
unit in cooling operation
Provides refrigerant to indoor
unit in heating operation
Provides refrigerant to indoor
unit in cooling operation
Pressure differential control
- 107 -
Specifications
R
= 15k
0
R
= 3460
0/80
1
1
exp
R = 15
3460
t
273
0°C[32°F] : 15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
AC220-240V
Open while being powered/
closed while not being pow-
ered
DC12V
Opening of a valve driven by a
stepping motor
0-2000 pulses
Check method
Continuity
check with a
tester
Same as
indoor LEV
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp250Pury-rp300yjm-a

Table of Contents