Mitsubishi Electric PURY-RP200 Service Handbook page 230

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
Both for MA remote controller and ME remote controller
1. Phenomena
Although cooling operation starts with the normal remote controller display, the capacity is not enough
(1) Cause, check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure
Pressure drops excessively.
2.
Indoor unit LEV malfunction
Insufficient refrigerant flows due to LEV malfunc-
tion (not enough opening) or protection works and
compressor frequency does not rise due to pres-
sure drop.
Refrigerant leak from LEV on the stopping unit
causes refrigerant shortage on the running unit.
3.
RPM error of the outdoor unit FAN
Motor failure or board failure, or airflow rate de-
crease due to clogging of the heat exchanger
The fan is not properly controlled as the outdoor
temperature cannot be precisely detected by the
temperature sensor.
The fan is not properly controlled as the pressure
cannot be precisely detected by the pressure sen-
sor.
HWE10020
Cause
Check method and remedy
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual
pressure with self-diagnosis LED.
-> If the accurate pressure is not detected, check
the pressure sensor. (Refer to the page on Trouble-
shooting of Pressure Sensor)(page 229)
Note:
Lower inlet pressure by the low pressure sensor
than the actual pressure causes insufficient capac-
ity.
SW1 setting
High pressure sensor
Low pressure sensor
(2)
Check temperature difference between the evapo-
rating temperature (Te) and the target evaporating
temperature (Tem) with self-diagnosis LED.
Note: Higher Te than Tem causes insufficient capacity.
SW1 setting
Evaporating temperature Te
Target evaporating temperature Tem
Note: Protection works and compressor frequency does
not rise even at higher Te than Tem due to high dis-
charge temperature and high pressure.
At high discharge temperature:
Refer to 1102.(page 155)
At high pressure:
Refer to 1302.(page 157)
Refer to the page of LEV troubleshooting ([4] -5-
).(page 235)
Refer to the page on troubleshooting of the outdoor
unit fan.
Refer to 5106.(page 177)
Refer to 1302.(page 157)
- 221 -
SW1
1 2 3 4 5 6 7 8 9 10
ON
SW1
1 2 3 4 5 6 7 8 9 10
ON
SW1
1 2 3 4 5 6 7 8 9 10
ON
SW1
1 2 3 4 5 6 7 8 9 10
ON
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp250Pury-rp300yjm-a

Table of Contents