Mitsubishi Electric PURY-RP200 Service Handbook page 28

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ II Restrictions ]
Reusability of MA remote controller wiring
NO
Is the shielded
wiring used?
YES
NO
Is the 2-core cable used?
YES
NO
Is the wiring length
less than 200m?
YES
Go to "Reusability of
Transmission line".
Reusability of System controller wiring
NO
Is the shielded
wiring used?
YES
NO
Is the 2-core cable used?
YES
If the wiring is more than 10m, include the
exceeding length to the total wiring length.
When 10m is exceeded, use the shielded
cable for exceeding length.
YES
Go to "Reusability of
Transmission line".
Table A
Type of cable
Cable size
Remarks
Connected with simple remote controller.
HWE10020
Please contact MITSUBISHI
ELECTRIC.
Refer to Table A.
Handle the non-using wiring as
shown in figure A.
Make wiring length less than
200m.
Please contact MITSUBISHI
ELECTRIC.
Refer to Table A.
Handle the non-using wiring as
shown in figure A.
(L
)
Transmission cables
i
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25
[AWG16]
Reusability of M-NET remote controller witing
NO
Is the shielded
wiring used?
YES
NO
Is the 2-core cable used?
YES
NO
Is the wiring of
less than 10m?
YES
Go to "Reusability of
Transmission line".
Figure A. Non-using wiring
Side:
Close to power supply unit
(Outdoor unit, Power supply unit)
Non using wiring on the power supply side (Outdoor unit, Power supply
unit) should be connected to the shield terminal. The non-using wiring on
the opposite side should be open and insulated.
ME Remote controller cables
Sheathed 2-core cable (unshielded)
CVV
2
0.3 1.25
[AWG22 16]
2
(0.75 1.25
[AWG18 16])
When 10m [32ft] is exceeded, use the
shielded cable for exceeding length.
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV
: PV insulated PVC sheathed control cable
- 19 -
Please contact MITSUBISHI
ELECTRIC.
Refer to Table A.
Handle the non-using wiring as
shown in figure A.
If the wiring is more than 10m, include the
exceeding length to the total wiring length.
When 10m is exceeded, use the shielded
cable for exceeding length.
shielded wire
MA Remote controller cables
2
0.3 1.25
[AWG22 16]
2
(0.75 1.25
[AWG18 16])
Max length : 200m [656ft]
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp250Pury-rp300yjm-a

Table of Contents